Precautions regarding lightning
In areas highly exposed to lightning, it may be advisable to
install a lightning arrestor upstream of inverter to safeguard it
against irreversible damage.
Precautions regarding overheating of the appliance
This appliance is designed to be mounted on a vertical wall or
partition as indicated herein.
It is imperative that there be a gap of 150mm around the inverter.
The installer must ensure that the temperature of the air at the
input is lower than 50°C in extreme operating conditions.
Measures should also be taken to allow evacuation of hot air on
either side of the inverter.
It's strictly forbidden to put any device on or against the inverter.
The inverter must not be installed near a heat source; it should be
installed in a well-ventilated area. The inverter's air inlets and
outlets must not be obstructed.
Attention hot surface: do not touch the inverter during
and after its operation (burn hazard).
Precautions regarding dust, seepage and falling water
The inverter should be located so as to prevent penetration of
damp, liquid, salt and dust, any of which could cause irreparable
damage to the equipment and be potentially hazardous for the
user.
The appliance should be installed in a dry and well-ventilated place.
P 18