Dual Service
Remove the two screws (Figure 7) securing the divider and remove
divider from Junction Box allowing (2) compartments to share a
combined space. A conduit connection is required for each
compartment that will be powered. Use large or small compartment
for Power or Data.
Large
Compartment
Power or Data
Ground Wire
(1) Divider
Figure 7
5.0 Electrical devices:
5.1 IMPORTANT! Select Electrical Devices (receptacles) to fit Poke-Through.
5.1.1 Side gangs:
– Use only 20A Duplex or Rectangular Receptacles in Side Gangs. GFCI
receptacles WILL NOT FIT in Side Gangs. Select receptacles with a 1.570" (39.8
mm) Max width or smaller to fit Side Gangs (see Figures 9 and 10).
5.1.2 Center gangs:
– Center Gang will accept 20A GFCI Receptacles, Rectangular, Duplex, Round, or
up to a 30A Twistlock device. NOTE: for Round or Twistlock devices, a special
power plate (RPT6-DPC-R) is required and must be ordered separately.
5.1.3 Remove side ears on devices:
– The side ears on the Devices must be removed for proper installation.
(see Figure 9 and 11)
CAUTION:
• If a 30A device is used in center gang, the supplied
grounding wire must be replaced with 10 AWG (not
supplied). (Ref. NEC Table 250.122 Equipment
Grounding)
5.1.4 Single Service
– Remove both dividers from the Junction Box allowing (3) compartments to
share the combined space. A conduit connection is required to the
compartment when it will be powered. Use combined compartment for
Power or Data.
Ground Wire
Figure 8
Ground Wire
Small
Compartment
Power or Data
Ground Wire
Remove divider
screws (2)
Ground Wire
(1)Large
Compartment
Power or Data
Remove all Side Ears
for Side and Center Gangs
1.570" Max width of
Side Gang
Receptacle
Figure 9
1.570" Max. width of
Side Gang
Receptacle
Use only Duplex
or Rectangular
Receptacles in
Side Gangs
3-Gang
Recessed
Mounting
Side
Surface
Gang
Figure 10
3 of 24 - ENGLISH
SIDE GANGS
1.570" Max. width of
Side Gang
Receptacle
GFCI, Round
or Twistlock
Devices will
ONLY fit in
Center Gang.
Use optional
Power Plate
RPT6-DPC-R
for Round or
Twistlock
Devices. See
Figure 25.
Side
Gang
Center
Gang