4. SETTINGS VIA CIRCUIT BOARD CONTROLLER
4.1. ADJUSTING THE WATER TEMPERATURE
4.1.1. Adjusting the maximum water temperature for cooling
By reducing the water temperature setting, the unit will start later. If the water temperature is set higher, the unit will
start sooner.
The default setting of this unit is cooling condensation (deep cooling). If you only wish to cool non-condensing (light
cooling), then you need to adjust the water temperature setting to 24°C.
1. Start setup mode: press and hold the [-] button until the blue LED flashes 5x and release.
2. Short press the [-] or [+] button to adjust the set temperature.
Automatic control: The
set temperature
3. Exit setup mode: hold the [-] button until the blue LED flashes 5x and release.
4.1.2. Adjusting the minimum water temperature for heating
By increasing the water temperature setting, the unit will start later. If the water temperature is set lower, the unit will
start sooner.
In combination with a heat pump, it may be necessary to reduce the water temperature.
1. Start setup mode: Press and hold the [+] button until the red LED flashes 5x and release.
2. Short press the [-] or [+] button to adjust the set temperature.
Automatic control: The
temperature.
3. Exit setup mode: press and hold the [+] button until the red LED flashes 5x and release.
After 30 seconds, the new settings are automatically saved and the device returns to the selected mode.
72
12 ̊ C
14 ̊ C
16 ̊ C
18 ̊ C
The blue LED flashes quickly when the minimum temperature is
reached.
The red LED flashes quickly when the maximum temperature
is reached.
green LED
lights up when the water temperature (supply water) is lower than the
24 ̊ C
26 ̊ C
28 ̊ C
30 ̊ C
The blue LED flashes quickly when the minimum temperature is
reached.
The red LED flashes quickly when the maximum temperature
is reached.
green LED
lights when the water temperature (supply water) exceeds the set
JAGA NV | BRIZA XS - ON/OFF | MANUEL | 26.09.2024 | V.1.05
20 ̊ C
22 ̊ C
24 ̊ C
26 ̊ C
32 ̊ C
34 ̊ C
36 ̊ C
38 ̊ C

Publicité