Télécharger Imprimer la page

Jaga BRIZA M - PLUG &PLAY Manuel page 46

Publicité

140
Min.120
29
1.2. INSTALLATION
01
562
122
Min.120
Unclip the front plate by pressing the spring clips on the side.
Check for a control module! Remove the casing and
disconnect the control module.
85
03
39
130
259
Install the condensate drain. The condensate drain system should
be fitted with a siphon to prevent odours. The siphon can be either
on the unit or on the final condensate connection (downstream
from the condensate trap). Pour water into the condensate trap
and check that it drains normally. If not, check the drain angle.
46
80
315
90
10
50 80
76
48
29
445
JAGA NV | BRIZA M - PLUG & PLAY - JRT-100TW | MANUEL | 26.09.2024 | V.1.02
02
Mark and drill the mounting holes. Place the device.
Use plugs that are suitable for the type of wall.
04
1/2"
1/2"
108
Make the hydronic connection.
95
When using devices for cooling: iron
couplings prohibited.
150
425
257
84
25
50
Use a back wrench when
fastening the hydronic
connections
If the unit is used for
cooling, the hydronic pipes
must be insulated.