Stripping length depends on the filter size
How to connect the filter:
1. Loosen three screws 0 and remove the terminal cover 1
2. Connect filter input cable to terminals 1U1, 1V1, 1W1 and PE.
Connect filter output cable to terminals 1U2, 1V2, 1W2 and PE.
– Observe tightening torques!
– The PE connection must comply with EN 61800−5−1.
3. The shield must be connected with a large surface to the shield sheet (PES).
– Turn down the shield and use metal cable binders to fix it (not included in the
scope of supply, e.g. EZAMBKBM) 2.
– Alternative: Insert shield mounting kit EZAMBHXMxxx (not included in the scope
of supply) and mount cable binders in addition for strain relief 3.
4. Insert terminal cover 1 and fix it with three screws 0.