c) Put in position the pressure detector directly on the burner injector afterward open the relative burner
knob at maximum position keeping it pressed, then measure the outlet pressure from the burner
injector.
d) Once the pressure checking has been carried out, replace the burner cap and flame spreader in the
correct and original position and re-connect electric power to the appliance.
8. Turn on appliance control cock and light each burner. Check for a clear blue flame without yellow tipping.
If burners show any abnormalities check that they are located properly and in line with the injector nipple.
9. Sometimes the burners will not ignite immediately and seem to 'blow' slightly when they do ignite. This
usually due to air in the gas lines, which will clear itself within seconds.
10. If after following the instructions given, satisfactory performance cannot be obtained, contact the local
gas authority for advice and assistance.
Electrical connection
The appliance is equipped with a 4 ft. (1.2 m.) flexible metal cable with 4 wires ready for connection to a
dedicated 4 wire grounded power supply/junction box: (fig.13)
Voltage 120/208 V a.c., Frequency 60Hz. Max Current: 3600W /20,2 A
Voltage 120/240 V a.c., Frequency 60Hz. Max Current: 4500W /22,2 A
A dedicated line and junction box should be used to connect the oven to a 25 A circuit.
Wiring diagrams
Fig. 25.
Room ventilation – Location and venting.
ATTENTION: An exhaust fan may be used with the appliance; in each case it shall be installed in
conformity with the national standards in force.
ATTENTION: Exhaust hood operation may affect other vented appliances; in each case it shall be
installed in conformity with the national standards in force.
Conversion to different types of gas
Before carrying out any maintenance work, disconnect the appliance from the gas and electric
supply. For Natural Gas fit regulator assembly described in Fig. 10. For LP Gas fit assembly
described in fig. 10.
- CHANGING THE NOZZLES FOR USE WITH OTHER TYPES OF GAS:
To change the nozzles of the burners use the following procedure:
Lift up the burners and unscrew the nozzles ( Fig. 14) using an adjustable spanner of 7 mm and change the
nozzles with those designed for the new gas supply according to the information given in TABLE A shown
below.
TABLE A: Adapting to different types of gas
Burner
Inner
Dual
burner
Outer
CAUTION: save the orifices removed from the appliance for future use
Black wire: connect to L1 (hot)
Red wire: connect to L2 (hot)
White wire: connect to N (neutral)
Green wire: connect to GND (ground)
Inj. size
Gas
1/100mm
Type
80
NG
50
LP(Propane)
N°2 x 130
NG
N°2 x 83
LP(Propane)
Pressure
Max Rate
[i.w.c.]
[BTU/h]
4"
2730
11"
2900
4"
15000
11"
16400
7
Min Rate
[W]
[BTU/h]
[W]
799
900
264
849
900
264
4394
4500
1318
4804
4500
1318
By-pass size
[1/100mm]
Regulated
29
Regulated
65