Product components (Fig. 3)
A Fitting frame
B Plug connection
C Sensor enclosure with lens
D Designer trim
4. Installation / wiring
• Switch OFF power supply. (Fig. 4)
A clip-on ceiling adapter or a frame for fitting onto a mounting box is provided
(Fig. 5).
– Wiring diagram (Fig. 6)
Wiring up the sensor switch: under section 6 of VDE 0100520, a multi-core lead
containing both the mains voltage leads as well as the control leads (e.g. NYM
5 × 1.5 mm²) may be used for the wiring between sensor and DALI Application
Controller.
The lead between DALI Application Controller and sensor must be no longer
than 300 m (with 1.5 mm²). After installing and switching ON, the sensor flashes
for 10 seconds.
Connecting the mains power supply lead (Fig. 6)
Note on parallel connection:
Several sensors can be connected in a DALI-2 system. In this case,
the maximum number of DALI users must not be exceeded
(➜ "10. Technical specifications")