UK | 10 Commissioning
LEDs
LED flashing modes:
42
Parameter
Set value /
ventilation level
Power units
0
(LT) or
1
room air
2
controls
3
(RLS)
4
5
6
230 V AC
1
input
2
3
4
5
6
Sensors
0
1
2
3
4
5
6
7
LED flashing rapidly
Setting /
description
Operation without further LT/RLS
Operation with 1 LT or RLS
Operation with 2 LT or RLS
Operation with 3 LT or RLS
Slave no. 1
Slave no. 2
Slave no. 3
Adjuster for adding further room air
controls (RLS) or power units (LTs) to
this room air control. Example: Two
further RLS (RLS #2 and #3) are con-
nected to RLS #1. Set value = 2. Set
set value 4 on RLS #2 and set value 5
on RLS #3.
Notice: Only single-type RLS combi-
nations are permitted!
Sleep mode
Intermittent ventilation
Safety shutdown
Supply air operation without overrun
Supply air operation with overrun time
of 6 min.
Supply air operation with overrun time
of 15 min.
For setting an additional function.
This can be activated with a button
or switch at the 230 V input.
No sensor
1 internal sensor
1 internal sensor + 1 external sensor
1 internal sensor + 2 external sensors
1 internal sensor + 3 external sensors
0 internal sensors + 1 external sensor
0 internal sensors + 2 external sensors
0 internal sensors + 3 external sensors
Select how many internal and external
sensors are connected/combined.
The PP 45 HYI internal sensor and
the PP 45 HY, PP45 CO2 and PP 45
VOC external sensors are available.
LED flashing slowly

Publicité

loading

Ce manuel est également adapté pour:

Ppb 30 kRls 45 oRls 45 k