6 EN – Quick installation guide
Select the power cables
Current: Select a cable capable of carrying the maximum load current and suitable for
the prospective short-circuit provided by the supply network. The method of
installation and ambient temperature affect the cable current carrying capacity. Obey
local regulations and laws.
Temperature: For an IEC installation, select a cable rated for at least 70 °C (158 °F)
maximum permissible temperature of conductor in continuous use. For North America,
select a cable rated for at least 75 °C (167 °F).
Voltage: 600 V AC cable is accepted for up to 500 V AC. 750 V AC cable is accepted
for up to 600 V AC. 1000 V AC cable is accepted for up to 690 V AC
Ensure the cooling
EN
See chapter
Technical data and references
and required cooling air flow.
DA
Check the grounding system compatibility
DE
The standard drive with no EMC filter or with EMC filter +E210 and the ground-to-phase
varistors connected can be installed to a symmetrically grounded TN-S system. If you install
ES
the drive to another system, you may need to disconnect the EMC filter and ground-to-phase
varistors. See ACS880 frames R1 to R11 EMC filter and ground-to-phase varistor
disconnecting instructions
FI
WARNING! Do not install the drive with EMC filter option +E202 connected to a
system that the filter is not suitable for. This can cause danger, or damage the
FR
drive.
IT
Note: When EMC filter +E202 is disconnected, the drive EMC compatibility is considerably
reduced.
NL
WARNING! Do not install the drive with the ground-to-phase varistor connected to
a system that the varistor is not suitable for. If you do, the varistor circuit can be
damaged.
PL
WARNING! Do not install the drive on a corner-grounded or midpoint-grounded
PT
delta system. Disconnecting the EMC filter and ground-to-phase varistor does not
prevent damage to the drive.
RU
SV
TR
ZH
(page 97) for the allowed ambient conditions