3.

Safety Distances

Within a radius of 100 cm in front of and 40 cm
around the stove, flammable, combustible, or heat-
sensitive materials (e.g. furniture, wood or plastic
panelling, curtains, etc.) are not allowed to be locat-
ed in the heat radiating area of the fire box window
(fig. 1).
Outside the radiation area of the fire box win-
dow, a safety distance of 15 cm* or 12 cm (when
situated in a corner) to flammable materials
is to comply sideways and behind the stove
(fig. 1). Above the stove, the safety distance of
75 cm to flammable materials has to be complied
with.
No flammable or temperature-sensitive materials
may be present within a radius of 20 cm around the
flue pipe connection (wall or room ceiling).
For particularly temperature-sensitive materials like
glass, larger distances may be necessary.
WARNING!
Flammable flooring materials (e.g. wood,
laminate, carpeting etc.) must be protect-
ed with a floorplate made of non-combus-
tible material (e.g. tiles, safety glass, slate,
or sheet steel).
The size of the floorplate must be larger
than the base of the stove by at least
60 cm in front and at least 22 cm at the
sides of the stove (fig. 2).
40
fig. 1
Dimensions in cm
22
22
floorplate
60
fig. 2
Dimensions in cm
* For highly-insulated components with a thermal
insulation resistance of R ≤ 6 m²K/W, there should
be a gap of 20 cm.
4.
Connection of Multiple Devices in
Direct Vent Operation
When the Luno B.13 is operated as a direct vent
model, more than one device can be connected to
the chimney under the following conditions:
CAUTION!
Multiple appliances per chimney are per-
mitted in line with the applicable national
and regional regulations.
All connected fireplace stoves must be in
the same building unit or in the same ef-
fective area of the ventilation system.
The inlets for the combustion air ducts are
located in areas of equal pressure (same
pressure ratios), wind-induced pressure
fluctuations have to be avoided.
The inlets for the combustion air ducts are
located in areas of equal pressure (same
pressure ratios), wind-induced pressure
fluctuations have to be avoided.
NOTE!
In England (UK), according to the appli-
cable building regulations (The Building
Regulations 2010: Combustion appliances
and fuel storage systems, point 1.25),
each solid-fuel appliance is required to
have its own chimney.