9
Overview of the unit
Method B
(One zone control)
Method C
(Two zone control)
POWER IN
82 / 276 EN
Voltage
Maximum running current (A)
Wiring size (mm
There are three methods for connecting the
thermostat cable (as described in the picture
above) and it depends on the application.
•
Method A (Mode set control)
RT can control heating and cooling individually,
like the controller for 4-pipe FCU. When the
hydraulic module is connected with the external
temperature controller, user interface set ROOM
THERMOSTAT to MODE SET:
POWER
A.1 When unit detect voltage is 230VAC between
IN
C and L1, the unit operates in the cooling mode.
A.2 When unit detect voltage is 230VAC between
H and L1, the unit operates in the heating mode.
A.3 When unit detect voltage is 0VAC for both
side (C-L1, H-L1) the unit stop working for space
heating or cooling.
A.4 When unit detect voltage is 230VAC for both
side (C-L1, H-L1) the unit working in cooling
mode.
•
Method B (One zone control)
RT provide the switch signal to unit. User interface
set ROOM THERMOSTAT to ONE ZONE:
B.1 When unit detect voltage is 230VAC between
H and L1, unit turns on.
B.2 When unit detect voltage is 0VAC between H
POWER IN
and L1, unit turns off.
Heat Pump Monobloc Inverter / User Manual
220-240~VAC
)
0.75
2
0.2