Installation and Operating Instructions
EN
Compact Ventilation Units AIR1 XC
Alarm
Sensor error EAF pressure
Frequency converter alarms
Alarm frequency converter SAF
Alarm frequency converter EAF
Communication error frequency
SAF
Communication error frequency
EAF
Warning frequency converter
SAF
Warning frequency converter
EAF
Communication errors expansion uits
Communication error expansion
unit 1
Communication error expansion
unit 3
Communication error expansion
unit 4
Communication error expansion
unit 5
Diverse
Fire alarm
External operating switch
Restart blocked after power-on
Internal battery failure
DX External unit
Rotation sentinel exchanger
Priority
Stop
Check/Solution
B
Yes
• Check Extract air Pressure transmitter and pressure hoses
(also inside pressure sensor)
A
YES
• Check motor and wiring
A
YES
• Check motor and wiring
A
YES
• Supply air fan not receiving Modbus signal
• Check wiring of power supply
• Check Modbus wiring from fan to controller
A
YES
• Exhaust air fan not receiving Modbus signal
• Check wiring of power supply
• Check Modbus wiring from fan to controller
C
No
• Cause dependent on motor type. Contact service
team
C
No
• Cause dependent on motor type. Contact service
team
C
No
• No communication with controller E15 of DX cooler
A
YES
• Communication with pressure sensor supply air fan inter-
rupted
• Check Modbus wiring from pressure sensor to controller
A
Yes
• Communication with pressure sensor extract air fan
interrupted
• Check Modbus wiring from pressure sensor to controller
A
YES
Communication is interrupted to the pressure sensor
AIR1-CAP (accessory for constant pressure control)
• Check Modbus wiring from pressure sensor to controller
A
Yes
If the alarm is unwarranted:
• Check connection to terminal strip (on-site contact)
• Can be programmed as NC or NO
• If the fire alarm has been triggered by the duct smoke
sensor RMK, it must be reset again. This is achieved by
disconnecting the AIR1 unit from the mains power supply
using the main switch.
C
Yes
• External operating switch is activated
• Check wiring
B
Yes
• Fan not running despite voltage recovery
A
No
• Replace battery CR2032 in controller
B
No
• Contact support of air conditioning system
B
YES
• Communication with rotary exchanger interrupted
• Check rotary heat exchanger
• Check rotation sentinel position and wiring
61