Helios AIR1 XC 500 L Notice De Montage Et D'entretien page 100

Table des Matières

Publicité

Installation and Operating Instructions
EN
Compact Ventilation Units AIR1 XC
Timer priorities (highest priority first):
• Timer Intensive
• Timer Normal or VOD (higher ventilation requirement)
• Timer Minimal
• Timer Recirculation
If the set timer times overlap, e.g. if the "Intensive" timer and the "Normal" timer are programmed for the same time, the
timer with the higher priority will be activated and the ventilation unit will be operated at the "Intensive" ventilation stage.
Special features in case of simultaneous programming of recirculation timer and VOD timer:
• If the VOD timer and recirculation timer are active at the same time and no air quality sensors reach the sensor limits
(intensive ventilation), the unit will switch to recirculation mode.
• If a connected sensor reaches the sensor limit, the recirculation mode will stop and the unit will run in sensor-con-
trolled operation (VOD).
• If the sensor signal reaches the sensor limit, the unit will switch back to recirculation mode.
• The recirculation mode will not work if the minimal, normal or intensive timers are running at the same time, since
it has a lower priority.
c� Holiday
Up to 24 separate holiday periods can be set for a whole year.
Set holiday calendar:
• Log on as User or Administrator
• Call up the "Timer settings" menu
• Holiday according to programme "Set daily/weekly programme". The ventilation unit always runs pursuant to the-
holiday settings during holiday periods
• Call up holiday calendar
• Set holiday periods
Holiday (mm:dd)
1: XX-XX – XX-XX
2: XX-XX – XX-XX
3: XX-XX – XX-XX
4�1�3 Sensor-controlled operation (VOD - Ventilation on demand)
The sensor-controlled operation function (Ventilation on demand = VOD) must first be set in the commissioning
assistant.
The sensor-controlled operation only works in "Constant volume flow mode" or "Constant speed mode". The sen-
sor-controlled operation function can only be activated using the VOD timer.
The sensor-controlled operation is only used to achieve improved room air quality. In this respect, the use of air quality
sensors (AIR1/KWL-CO2 0-10V, KWL-FTF 0-10V, AIR1/KWL-VOC 1-10V) is required. This mode can also be used for
multiple connected sensors. A signal converter (AIR1-SK) must be used if more than 3 sensors are to be connected.
The sensor with the highest ventilation requirement determines the ventilation operation mode.
Ventilation
Hysteresis
window
High
stage
Low stage
or minimal
ventilation
Start: Activation
low stage
• Minimal: Activation of ventilation stage "minimal"
• Intensive: Activation of ventilation stage "intensive"
• Diff: hysteresis
OK
OK
Hysteresis
window
CO2 / VOC / relative
humidity measurement
Activation
high stage
37
OK
OK

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Air1 xc 700 lAir1 xc 1400 lAir1 xc 500 rAir1 xc 700 rAir1 xc 1400 rAir1 xc 2200 l ... Afficher tout

Table des Matières