 Check the fastening of all terminals inside the electrical box (every four months)
 Visually check the refrigerating circuit completely, also inside the machines, in order to detect
refrigerant leaks, that are also put in evidence by traces of lubricant oil. Make a fast intervention
and further check in case of doubt . (every four month)
 Periodically clean the unit in order to avoid deposits of toxic substances. The use of water and soap
is recommended and avoid using solvents , aggressive agents , abrasive or ammonia-based
materials.
 In the event that machine parts need replacing, they have to be replaced by items exactly the
same to the originals ones
Important: once the maintenance is accomplished, replace all safeties previously removed (housing
and grid ; see Drawing 8-9).