ADJUSTING THE FLOW RATE
Ceramic cartridge Ø 40mm:
• Washbasin/sink mixers: Flow rate limited to 5 lpm at 3 bar.
• Shower mixers: Flow rate limited to 8 lpm at 3 bar.
Ceramic cartridge Ø 40mm with EP pressure balancing (see operation principles
• Flow rate limited to 5 lpm at 3 bar.
ADJUSTING THE TEMPERATURE
Temperature limiter:
• All hospital mixers are fitted with the maximum temperature limiter pre-set at the factory.
Where thermostatic mixing valves are installed the temperature limiter
MUST BE REMOVED from all point-of-use mixers.
• Recommended maximum temperature settings for UK healthcare applications are: bidets 38°C,
washbasins and showers 41°C. For all other countries please refer to the relevant hot water safety guidelines.
Adjusting the mixed water temperature limiter:
To adjust the pre-set maximum temperature, unclip and reposition the index ring located
beneath the control lever.
• The position of the index ring will limit the water temperature at the mixer outlet.
• To access the cartridge (Fig. E), remove the control lever by removing the cover cap a,
unscrew the grub screw b using a 2.5mm Allen key, and unscrew the collar c from the mixer body.
• To change the hot water (HW) setting (Fig. F-1), unclip the index ring a and turn clockwise to lower
the temperature, or anti-clockwise to increase it. Replace the index ring and check the temperature
at the mixed water outlet to achieve the desired maximum temperature.
• To return to the maximum hot water position (Fig. F-2), align the marker on the index ring b
with the marker on the cartridge c.
• For model 2538, change the hot water setting as follows: unclip the index ring a
from its initial setting (Fig. F-1) and turn anti-clockwise to reduce the hot water temperature,
or clockwise to increase the temperature.
MAINTENANCE
• Our mixers will withstand thermal and chemical shocks as described by current guidelines.
• Check the operation of the pressure-balancing cartridge and the anti-scalding safety at least
once a year, and more frequently if necessary. In case of malfunction, replace the cartridge.
• Non-return valves and filters must be checked at least once a year and more often if the water quality
necessitates. In the event of malfunction, de-scale or replace worn or damaged parts.
• Across all mixers, the torque required to hold the cartridge in the mixer body should be between 8
and 10 Nm to avoid leaks.
Note: In the event of a leak on the mixers with swivel spouts, replace the 2 waterproof lip seals.
MAINTENANCE & CLEANING
• Cleaning chrome: Do not use abrasive, chlorine or any other acid-based cleaning products.
Clean with mild soapy water using a cloth or a sponge.
• Frost protection: Drain the pipes and operate the mixer several times to drain any remaining water.
For UK market only: Tel. 01491 821 821 email: technical@delabie.co.uk
For all other markets: Tel. +33 (0)3 22 60 22 74 email: sav@delabie.fr
After Sales Care and Technical Support:
The installation guide is available on: www.delabie.co.uk
The installation guide is available on: www.delabie.com
EN
(Fig. D
)):

Publicité

loading

Ce manuel est également adapté pour:

240025002700