WIKA MHC-1 Mode D'emploi page 20

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

8. Faults
Faults
No cyclic transmission
EN
Signal span too small/drops
Signal span varies/inaccurate
Deviating zero point signal
If complaint is unjustified, we will charge you the complaint processing fees.
Error codes
The error codes can be found under "Additional instructions"
The "Additional instructions" are available for download at www.wika.com.
CAUTION!
If faults cannot be eliminated by means of the measures listed above, shut down the
instrument immediately, and ensure that pressure and/or signal are no longer present,
and secure the instrument from being put back into operation inadvertently. In this case,
contact the manufacturer. If a return is needed, please follow the instructions given in
chapter 9.2 "Return".
20
Causes
PDO mapping
Transmission type incorrect
Mechanical overload caused by
overpressure
Sealing/sealing face damaged/soiled,
sealing does not have a tight fit, threads
jammed
Operating temperature too high/low
Strongly varying pressure of the process
medium
Operating temperature too high/low
Overpressure limit exceeded
WIKA operating instructions pressure sensor, model MHC-1
Measures
Check the configuration parameters
Replace instrument
Clean the sealing/sealing face,
replace sealing if applicable
Observe the permissible
temperatures
Damping; consulting by the
manufacturer
Permissible temperatures
Observe the permissible
overpressure limit

Publicité

Table des Matières
loading

Table des Matières