7.3 SETTING OF THE CONTACT TYPE OF THE LIMIT SWITCHES AS WARNING LIGHT FOR AUTOMATION 1 AND 2
With the following procedure it is possible to set the type of contact for both automations as a warning light.
PROCEDURE
STEP 1
With a paper clip makes a long press of the "hidden" button.
The LED turns on light blue/pink/yellow cyclically.
Release the key when the led is light yellow.
STEP 2
Press the button 1 on the receiver for a short time
NOTE:
if with limit switch in warning light mode a mode other than warning light is set for automation 1 or automation 2 (see provedura 7.1 and
7.2), the other limit switch is set to "no limit switch" mode
7.4 RESET OF THE CONTROL UNIT
This procedure let you take the control unit back to factory settings.
ATTENTION: the only parameter that will not be removed will be the association with the ONESMART application.
To edit or delete also this parameter, reed the procedure.
PROCEDURE
STEP 1
Hold the receiver button P1 down (about 4 seconds.) until the LED begins to Flash.
36
ACTION: Short press of button 1 LED: Count the number of Flashes
ACTION: Hold button RADIO down LED: Flashes red
x1
x1