APPLICATION
The HE260A,B Bypass Flow-Through Humidifier uses the warm air furnace
blower to provide humidification for the whole house. The HE260A,B works
with virtually any Honeywell humidity control, but for optimal performance,
use with the Honeywell Perfect Climate Comfort Center™ control.
INSTALLATION
WARNING
Hazardous Voltage.
Can cause Personal Injury or Equipment Damage.
Do not cut or drill into any air conditioning or electrical accessory.
CAUTION
Freezing Water and High Water or Static Pressure Hazard.
Can cause water damage or permanent equipment damage.
• The humidifier must be located where the ambient temperature is
above 32°F (0°C) and below 160°F (71°C).
• Be sure supply plenum static pressure is no greater than 0.3 in.
w.c. and water pressure is no greater than 125 psi.
IMPORTANT
To assure optimal product performance, be sure the template is
level before marking.
1. Determine the best location for the humidifier and draw a level line on
the plenum. See Fig. 1.
IMPORTANT
Mount the humidifier at least 3 in. (76 mm) above the furnace jacket
to allow adequate space for the solenoid valve and drain line. Check
that there is adequate space above the humidifier to remove and
install the humidifier cover. Do not install on a furnace jacket.
R I Z
H O
O Y
W B
L O
Fig. 1. Typical humidifier installation locations.
® U.S. Registered Trademark
Copyright © 1998 Honeywell Inc. • All Rights Reserved
All manuals and user guides at all-guides.com
Bypass Flow-Through Humidifier
READ AND SAVE THESE INSTRUCTIONS
L
T A
O N
O Y
H B
H I G
W N
D O
O
F L
M12248B
2. Tape the template in position and trace around the template.
3. Remove the template and carefully cut the rectangular opening.
4. Disassemble the humidifier; remove the cover and take out the
humidifier pad assembly. See Fig. 2.
NOTE: Sidewalls are interchangeable for either left or right
bypass installation. To change direction, remove the screws
holding each sidewall, switch sidewall locations and reinstall
the screws.
5. Position the humidifier housing in the opening (be sure it is level), so
the locking tabs are in place on the lower sheet metal edge of the
opening.
6. Secure the humidifier housing to the opening at the top and bottom
using sheet metal screws.
COVER
SIDEWALL
BYPASS SIDEWALL
Fig. 2. Humidifier components.
7. Locate the other plenum and cut an opening for a 6 in. (152 mm) collar.
8. Install the 6 in. (152 mm) collar.
NOTE: Be sure to install a duct damper for summer shutoff on
systems with air conditioning.
9. Install a 6 in. (152 mm) diameter duct from the collar to the humidifier.
NOTE: Some installations require a 90° elbow attachment to the
collar.
10. Seal the duct connections with duct tape.
NOTE: To avoid sagging and stress on the humidifier, add support
when ducting is longer than 4 ft (120 cm).
TEMPLATE
HE260A,B
INSTALLATION INSTRUCTIONS
WATER
FEED NOZZLE
HUMIDIFIER
PAD ASSEMBLY
FRAME
HUMIDIFIER
HOUSING
WATER
FEED TUBE
69-1106EF-3
M12304