Installation électrique
5
Installation conforme à la norme UL
Model (frame size)
MCX91A-0017-2.3-4-.. (0S)
MCX91A-0025-2.3-4-.. (0S)
MCX91A-0034-2.3-4-.. (0S)
MCX91A-0042-2.3-4-.. (0S)
MCX91A-0055-2.3-4-.. (0S)
MCX91A-0070-2.3-4-.. (0L)
MCX91A-0093-2.3-4-.. (0L)
MCX91A-0110-2.3-4-.. (0L)
Model (frame size)
MCX91A-0017-2.3-4-.. (0S)
MCX91A-0025-2.3-4-.. (0S)
MCX91A-0034-2.3-4-.. (0S)
MCX91A-0042-2.3-4-.. (0S)
MCX91A-0055-2.3-4-.. (0S)
MCX91A-0070-2.3-4-.. (0L)
MCX91A-0093-2.3-4-.. (0L)
MCX91A-0140-2.3-4-.. (0L)
MCX9.A-0213-2.3-4-.. (3)
50
Notice d'exploitation – MOVITRAC
WARNING - The opening of the branch-circuit protective device may be an indication
that a fault current has been interrupted. To reduce the risk of fire or electric shock,
current-carrying parts and other components of the controller should be examined and
replaced if damaged. If burnout of the current element of an overload relay occurs, the
complete overload relay must be replaced.
ATTENTION - LE DÉCLENCHEMENT DU DISPOSITIF DE PROTECTION DU CIR-
CUIT DE DÉRIVATION PEUT ÊTRE DÛ À UNE COUPURE QUI RÉSULTE D'UN
COURANT DE DÉFAUT. POUR LIMITER LE RISQUE D'INCENDIE OU DE CHOC
ÉLECTRIQUE, EXAMINER LES PIÈCES PORTEUSES DE COURANT ET LES
AUTRES ÉLÉMENTS DU CONTRÔLEUR ET LES REMPLACER S'ILS SONT EN-
DOMMAGÉS. EN CAS DE GRILLAGE DE L'ÉLÉMENT TRAVERSÉ PAR LE COU-
RANT DANS UN RELAIS DE SURCHARGE, LE RELAIS TOUT ENTIER DOIT ÊTRE
REMPLACÉ.
For maximum branch circuit protection see tables below.
Single-phase 200 – 240 V voltage range (SCCR: 65 kA)
Non-semiconductor
fuses (currents are
maximum values)
20 A/250 V
25 A/250 V
30 A/250 V
40 A/250 V
40 A/250 V
60 A/250 V
60 A/250 V
60 A/250 V
Three-phase 200 – 240 V voltage range (SCCR: 65 kA)
Non-semiconductor
fuses (currents are
maximum values)
6 A/250 V
6 A/250 V
10 A/250 V
15 A/250 V
20 A/250 V
25 A/250 V
30 A/250 V
30 A/250 V
60 A/600 V
Class: CA, CB, CD,
CF, G, J, K-1, K-5,
RK1, RK5, T
®
advanced
Inverse-time circuit
breaker (currents are
maximum, voltages mi-
nimum values)
20 A/240 V
25 A/240 V
30 A/240 V
30 A/240 V
30 A/240 V
30 A/240 V
30 A/240 V
30 A/240 V
Inverse-time circuit
breaker (currents are
maximum, voltages mi-
nimum values)
15 A/240 V
15 A/240 V
15 A/240 V
15 A/240 V
20 A/240 V
25 A/240 V
30 A/240 V
30 A/240 V
60 A/500 V
Type E combination mo-
tor controller, mfd by Sie-
mens, type Sirius
(rated 480 V/277 V)
3RV2011-1GA10, 6.3 A
3RV2011-1HA10, 8 A
3RV2011-1JA10, 10 A
3RV2011-4AA10, 16 A
3RV2011-4AA10, 16 A
3RV2011-4BA10, 20 A
3RV2011-4DA10, 25 A
3RV2011-4EA10, 32 A
Type E combination mo-
tor controller, mfd by Sie-
mens, type Sirius
(rated 480 V/277 V)
3RV2011-1AA10, 1.6 A
3RV2011-1CA10, 2.5 A
3RV2011-1EA10, 4 A
3RV2011-1EA10, 4 A
3RV2011-1GA10, 6.3 A
3RV2011-1HA10, 8 A
3RV2011-1JA10, 10 A
3RV2011-4AA10, 16 A
3RV2021-4DA10, 25 A