B Electrical Connections
ATTENTION INSTALLER
All electric wall ovens must be hard wired (direct
wired) into an approved junction box. A plug and
receptacle is NOT permitted on these products.
DO NOT shorten the flexible conduit. The conduit
strain relief clamp must be securely attached to the
junction box and the flexible conduit must be
securely attached to the clamp. If the flexible
conduit will not fit within the clamp, do not install the
oven until a clamp of the proper size is obtained.
NOTE TO ELECTRICIAN: The 3 power leads
supplied with this appliance are CSA recognized for
connection to heavier gauge household wiring. The
insulation of these 3 leads is rated at temperatures
much higher than the temperature rating of
household wiring. The current carrying capacity of
the conductor is governed by the wire gauge and
the temperature rating of the insulation around the
wire.
WARNING:
connection of aluminum house
wiring to copper leads can result in
an electrical hazard or fire. Use only
connectors designed for joining
copper to aluminum and follow the
manufacturer's recommended
procedure closely.
Installation Instructions
Improper
B1
Turn off the circuit breaker or remove fuses to
the oven branch circuit.
B2
With the oven supported on a table or platform
in front of the cabinet opening, connect the
flexible conduit to the electrical junction box as
shown below. Position the conduit in such a
manner that it will lie on top of the oven in a
natural loop when the oven is installed. You will
need to purchase an appropriate strain relief
clamp to complete the connection of the
conduit to the junction box.
Conduit
Place oven on a
support to assist in
connecting conduit
B3
This oven is supplied with a 123 cm (48") long
flexible conduit consisting of:
3 insulated conductors (copper)
1 insulated ground conductor (copper)
B4
Suggestion: Attach conductors to residence
wiring as shown by wiring diagram.
CONDUIT
FROM
OVEN
BLACK
GREEN
BLACK
GROUND
CSA APPROVED
JUNCTION BOX AND COVER
5
Junction Box
Location
BARE
GROUND
RED
WHITE
BLACK
Strain Relief Clamp
(not included)
must be used at
Junction Box
WHITE
(NEUTRAL)
CSA APPROVED
RED
CONNECTOR
TO BREAKER PANEL
WHITE
RED
#12-#10 AWG-COPPER
NMD90 WIRE. FUSE 20
AMP CIRCUIT BREAKERS
GROUND
WIRE