ENGLISH
10. Labelling
The equipment must be labelled stating that it has been taken out of service and drained
of refrigerant. The labelling must be dated and signed. Ensure that there are labels on the
equipment stating that the equipment contains flammable refrigerant.
11. Recovery
-
When refrigerant is removed from a system, either for service or decommissioning, it is
recommended good practice that all refrigerants are removed safely.
-
When transferring refrigerant to cylinders, ensure that only suitable refrigerant-recovery
cylinders are used. Ensure that the correct number of cylinders is available to support
the total load of the system. All cylinders to be used are designated for the refrigerant
recovered and labelled for that refrigerant (i.e., special refrigerant-recovery cylinders).
Cylinders must be completed with pressure-relief valves and associated shut-off valves
in good working order. Empty recovery cylinders are evacuated and, if possible, cooled
before recovery takes place.
-
Recovery equipment must be in good working order with a set of instructions concerning
the equipment at hand and must be suitable for the recovery of flammable refrigerants. In
addition, a set of calibrated weighing scales must be available and in good working order.
Hoses must be complete with disconnect couplings free of leakage and in good running
order. Before using the recovery machine, check that it is in good running order, properly
maintained, and that all associated electrical components are sealed to prevent ignition in
the event of refrigerant release. Consult the manufacturer in case of doubt.
-
The flammable refrigerant must be returned to the refrigerant supplier in the correct
recovery cylinder, and the applicable waste transfer note must be provided. Do not mix
refrigerants in recovery units and especially not in cylinders.
If compressors and compressor oils are to be removed, ensure that they have been drained
to an acceptable level so that no flammable refrigerant remains within the lubricant. The
evacuation process must be carried out before returning the compressor to the suppliers. Only
electrical heating of the compressor body should be used to accelerate this process. When oil
is drained from a system, it must be done in a safe manner.
7. TECHNICAL SPECIFICATIONS
Product: ForceClima 7100 SoundLess
Product reference: 08170
Power Supply: 220-240 V~, 50 Hz
Cooling power: 7000 BTU/h (2.06 kW)
Electrical power consumed (Cooling): 785 W
Electrical current consumed (Cooling): 3.5 A
72
FORCECLIMA 7100 SOUNDLESS