BMP 01-ZLZPP _ 1A- _ _ _ _ -00 -P _ _ /P _ _ -S4/P _ _ -S75
Magnetic Field Positioning System
6
Switching output
6.1
Switching output
When powered up the sensor is first in SIO
mode. After a restart (power cycle) or fallback
command the sensor reverts to SIO mode.
Switching signal (factory setting)
active
inactive
Fig. 6-1:
Switching signal (factory setting)
Taught-in switching signal
(Teach 1 (switch-on point) and Teach 2 (switch-off point)
carried out)
Teach 1
Teach 2
active
inactive
Teaching in possible in the complete
configured measuring range
Fig. 6-2:
Taught-in switching signal
N.O./N.C.
As standard, the switching output is configured as a
normally open contact (image above). It can be converted
to normally closed logic.
Teach 2
Teach 1
active
inactive
Teaching in possible in the complete
configured measuring range
Fig. 6-3:
Taught-in switching signal
For the adjustment process, see section 6.2 on
page 15.
www.balluff.com
6.2
Settings using the button
NOTICE
Damage from pointed objects.
Operating the button with pointed objects may result in
damage.
► Do not press the button with a pointed object.
For teaching do not user ferromagnetic
materials (e.g. screwdriver) since this could
result in interference!
It is also possible to apply a mode without
change (timeout or power cycle).