BMP 01-ZLZPP _ 1A- _ _ _ _ -00 -P _ _ /P _ _ -S4/P _ _ -S75
Magnetic Field Positioning System
4
Installation and connection (continued)
Installation using BAM TG-MP-028 magnet
Fig. 4-14: Spacing using BAM TG-MP-028 magnet
Fig. 4-15: Installation example
www.balluff.com
4.4
Electrical connection
BMP 01-...-P_ _-S75
2
4
1
3
M 8-4 (Class A)
Fig. 4-16: Plug connector pin assignment (top view on pin side)
Pin Wire color
Signal
1
Brown
+24 V (operating voltage UB+)
2
White
Do not connect
3
Blue
GND (operating voltage UB– ;
reference potential)
4
Black
OUT1 (switching output S1) or C/Q
(IO-Link)
Tab. 4-1:
Plug connector pin assignment
4.5
Cable routing
Magnetic fields
Ensure that there is sufficient distance between the BMP
and holding cylinder and any strong, external magnetic
fields.
Cable routing
Do not route cables between the BMP, control system and
power supply near power lines (inductive crosstalk
possible) and ensure EMC-compliant cable routing or
machine installation.
The cable must be routed tension-free.
Bending radius for fixed cable
The bending radius for fixed cable routing must be at least
triple the cable diameter.
Cable length
Cable length max. 20 m.
BMP 01-...-P_ _-S4
2
1
3
4
M 12-4 (Class A)
english
13