TC4-NVS/P
VENTILATION SETTINGS
Adjusting the Cooling Offset
The cooling offset ranges from 0 to 20.0
Turn the selection knob to OFFSET — STAGE 2. The current offset
flashes on the display.
Use the adjustment knob to set the offset to the desired value.
Adjusting the Cooling Differential
The cooling differential ranges from 0.5
Turn the selection knob to DIFFERENTIAL — STAGE 2. The current
differential flashes on the display.
Use the adjustment knob to set the differential to the desired value.
Adjusting the Minimum Ventilation Cycle
Time on and time off range from 0 to 900 seconds, in increments of 15
seconds.
Turn the selection knob to TIMER — STAGE 2. The current time on
is displayed, alternating with the word "On".
Use the adjustment knob to set time on to the desired value.
Press the push-button. The current time off is displayed, alternating
with the word "OFF".
Use the adjustment knob to set time off to the desired value.
28
TC4-NVS/P.rev.05
o
o
F ( 0 to 11.1
o
o
F to 20.0
F (0.3 to 11.1
C).
o
C).