STAGE 2 OPERATION
Stage 2 can be configured for cooling, heating, mist or recirculation. Use
internal dipswitches # 4, 5 and 6 to select a configuration.
1. COOLING
Stage 2 has two modes of operation when used for cooling: (i) Continuous
Mode — used when cooling is required to lower the room temperature; (ii)
Minimum Ventilation Mode — provides oxygen to the room and reduces
humidity levels when cooling is not needed.
Minimum Ventilation Cycle
When cooling is not required, Stage 2 fans operate according to the
minimum ventilation cycle.
ON
OFF
TIME ON [in seconds] - Time on is the portion of the minimum ventilation
cycle when Stage 2 fans are in operation.
TIME OFF [in seconds] - Time off is the portion of the minimum ventilation
cycle when the Stage 2 fans are turned off.
Minimum Ventilation Cycle Settings
1. To run the fans continously at minimum speed, set time off to
zero and time on to any value other than zero.
2. To stop the fans, set time on to zero and time off to any value.
26