Installation guide
Solenoid coil
Types AS, AU, and AZ
© Danfoss | Climate Solutions | 2021.12
50
−
60 Ncm (0.39
089
40
−
50 Ncm
PG 11
(0.30
−
0.39 lb-ft)
250
(1.84
Max. 8 mm (0.31 in)
Min. 4 mm (0.16 in)
AS
Plug
AU
Cable
AS / AZ
Spade
−
0.44 lb-ft)
(2.16 in)
r > 55 mm
−
375 Ncm
−
2.77 lb-ft)
Cable strain relief
ENGLISH
Type of control
1
Safety classification
Class I
Ambient temperature
6 W V AC NC valve
7 W V AC NC valve
14 W V DC
0 − 100% R.H. (0 − 97% R.H. non-condensation
Humidity
condition if IP level is below IPX5/NEMA X4)
-15% − 10%
Voltage variation
V AC
V DC
±10%
Ball pressure test
200 °C (392 °F)
Impulse withstand voltage
Cable
4.0 kV at altitude <4000 m (13123 ft)
Spade
4.0 kV at altitude <4000 m (13123 ft)
Plug
4.0 kV at altitude <2000 m (6561 ft)
Plug
3.1 kV 2000 m<altitude<4000 m
(6561<altitude<13123 ft)
Enclosure rate IPXX
Cable
IP67
Pollution degree PDX
Plug
IP65
Spades
IP00
Installation
Integrated control
Incorporated control
Independently mounted control
ø6.6 − ø11 mm (ø0.26 − ø0.43 in)
Suitable cable and
0.75 − 1.5 mm² (21 − 15 AWG flexible cord)
conductor size for plug
Number of mating for plug
10 times
Cable size
ø6.6 mm (ø0.26 in)
Cable conductor size
3 x 0.75 mm² (3 x 0.001 in
Installation and handling for cable: > 5 °C (41 °F)
- Only qualified personnel is allowed to install or maintain this product
- Disconnect the power when dismounting the coil
- Avoid direct exposure to alkaline conditions, use in neutral conditions is recommended
- Ensure that the O-ring is in place on the valve
- If the coil is used as independently mounted control, the end-user shall use a plastic cable
gland with strain relief
Special note for R290:
The 9 mm coil (IP65/67) is validated in accordance to ISO 5149, IEC 60335 (ref. IEC/EN 60079-
15). Ignition risk is evaluated in accordance to ISO 5149 and IEC 60335 (ref. IEC/EN 60079-15).
Please make sure that there is no spark, arc on the spade connection during the application.
Always Install a fuse ahead of the coil: rated current: two times of rated current, time lag:
medium, to avoid short circuit.
The coil used in an area of not more than pollution degree 2.
Follow the installation guide to mount the coil correctly, and apply o-ring for sealing to
prevent moisture penetrating inside the coil.
Safety note:
The 9 mm coil (IP65/67) can be applied on systems with R290 as the working fluid.
For countries where safety standards are not an indispensable part of the safety system
Danfoss recommends the installer gets a third party approval of any system containing
flammable refrigerant.
Please follow specific selection criteria stated in the datasheet for these particular
refrigerants.
Note that 9 mm coil (IP65/67) has NOT been verified ATEX or IECEx or IEC 60079 series zone
2 compliant. The product is only validated for systems in compliance with ISO5149, IEC
60335 (ref. IEC/EN 60079-15). It is the responsibility of the user to verify such compliance.
Improper use can cause explosion, fire, leakage potentially causing death, personal injury,
or damage to property.
AN364239296111en-000201 | 1
-40 − 60 °C (-40 − 140 °F)
-40 − 50 °C (-40 − 122 °F)
-40 − 60 °C (-40 − 140 °F)
PD4
PD3
PD3
2
)