Index Size Acronym
79
1
FrcCompDesta-
bil_Circ2
90
2
rSPt
92
2
PwrReq
96
2
SrcSetP_Circ1
98
2
SrcSetP_Circ2
100
2
rps1
102
2
Mc1
104
2
MP1
106
2
Drt1
108
1
AlHs1_1
109
1
AlHs2_1
110
1
AlHs3_1
111
1
AlHs4_1
112
2
DxPwrReq
114
1
MotTyp
115
1
EnvelopeZone_Circ1 USINT
116
2
EnvPnt_X1
118
2
EnvPnt_Y1
120
2
EnvPnt_X2
122
2
EnvPnt_Y2
124
2
EnvPnt_X3
126
2
EnvPnt_Y3
128
2
EnvPnt_X4
130
2
EnvPnt_Y4
132
2
EnvPnt_X5
134
2
EnvPnt_Y5
136
2
EnvPnt_X6
138
2
EnvPnt_Y6
140
2
EnvPnt_X7
142
2
EnvPnt_Y7
144
2
EnvPnt_X8
146
2
EnvPnt_Y8
148
1
EnvelopeZone_Circ2 USINT
149
2
EnvPnt2_X1
151
2
EnvPnt2_Y1
153
2
EnvPnt2_X2
155
2
EnvPnt2_Y2
157
2
EnvPnt2_X3
159
2
EnvPnt2_Y3
161
2
EnvPnt2_X4
163
2
EnvPnt2_Y4
165
2
EnvPnt2_X5
167
2
EnvPnt2_Y5
169
2
EnvPnt2_X6
171
2
EnvPnt2_Y6
173
2
EnvPnt2_X7
175
2
EnvPnt2_Y7
177
2
EnvPnt2_X8
179
2
EnvPnt2_Y8
181
2
rps2
183
2
Mc2
185
2
MP2
187
2
Drt2
189
1
AlHs1_2
190
1
AlHs2_2
191
1
AlHs3_2
192
1
AlHs4_2
193
1
MotTyp2
203
1
EEV_Protection_Circ1 EEV_ProtectionSta-
204
1
EEV_Protection_Circ2 EEV_ProtectionSta-
205
1
EEV_Reg_Circ1
206
1
EEV_Reg_Circ2
207
2
AFE2
209
2
cUSr
211
2
PwrRunCircs_Perc
213
2
AFC2
215
2
AFE1
217
2
AFC1
219
1
IOprbCfgWrn
220
2
W_UsrTempRegPID
226
1
DfrStatus_Circ1
227
2
AIN_PwrReq_Circ1
231
1
SWverEXP
232
1
SWverMAIN
233
1
PWRP_ErrCode_Circ1 UDINT
234
1
PWRP_ErrCode_Circ2 UDINT
235
2
PwrReq_AC_Circ1
237
2
PwrReq_AC_Circ2
μchiller +0300053FR rel. 2.4 - 09.10.2023
Min
Max
DataType
R/W
Value
Value
UINT
R
REAL
R/W 0
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
UINT
R
UINT
R
UINT
R
UINT
R
REAL
R
UINT
R
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
UINT
R
UINT
R
UINT
R
UINT
R
UINT
R
R
tus(1..5)
R
tus(1..5)
INT
R
INT
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
UINT
R
REAL
R
UINT
REAL
R
UINT
R
UINT
R
-
-
R
-
-
R
REAL
-
-
R
REAL
-
-
R
Init
UoM
Description
Value
Destabilisation status for circ.2 (0=No comp. forcing
request , 1=Check if forcing is possible , 2=Enable to
force comp., 3=Wait status)
CELSIUS
rSPt - Remote set point
0
PERCENT
PwrReq - Power request
0
CELSIUS
SrcSetP_Circ1 - Source fan circ.1 set point
0
CELSIUS
SrcSetP_Circ2 - Source fan circ.2 set point
0
RPS
rps1 - Actual rotor speed coming from inverter
0
AMPERE
Mc1 - Current motor current [A]
0
KILOWATT
MP1 - Current motor consumption [kW]
0
CELSIUS
Drt1 - Current drive temperature [°C]
0
PSD circuit 1: the last alarm log
0
PSD circuit 1: the last-but-1st alarm log
0
PSD circuit 1: the last-but-2nd alarm log
0
PSD circuit 1: the last-but-3rd alarm log
PERCENT
Direct expansion capacity request
0
MotTyp - BLDC circ.1 Carel Database ID
0
EnvelopeZone_Circ1 - Envelope zone circ.1
0
CELSIUS
EnvPnt_X1 - Envelope point
0
CELSIUS
EnvPnt_Y1 - Envelope point
0
CELSIUS
EnvPnt_X2 - Envelope point
0
CELSIUS
EnvPnt_Y2 - Envelope point
0
CELSIUS
EnvPnt_X3 - Envelope point
0
CELSIUS
EnvPnt_Y3 - Envelope point
0
CELSIUS
EnvPnt_X4 - Envelope point
0
CELSIUS
EnvPnt_Y4 - Envelope point
0
CELSIUS
EnvPnt_X5 - Envelope point
0
CELSIUS
EnvPnt_Y5 - Envelope point
0
CELSIUS
EnvPnt_X6 - Envelope point
0
CELSIUS
EnvPnt_Y6 - Envelope point
0
CELSIUS
EnvPnt_X7 - Envelope point
0
CELSIUS
EnvPnt_Y7 - Envelope point
0
CELSIUS
EnvPnt_X8 - Envelope point
0
CELSIUS
EnvPnt_Y8 - Envelope point
0
EnvelopeZone_Circ2 - Envelope zone circ.2
0
CELSIUS
EnvPnt2_X1 - Envelope point
0
CELSIUS
EnvPnt2_Y1 - Envelope point
0
CELSIUS
EnvPnt2_X2 - Envelope point
0
CELSIUS
EnvPnt2_Y2 - Envelope point
0
CELSIUS
EnvPnt2_X3 - Envelope point
0
CELSIUS
EnvPnt2_Y3 - Envelope point
0
CELSIUS
EnvPnt2_X4- Envelope point
0
CELSIUS
EnvPnt2_Y4 - Envelope point
0
CELSIUS
EnvPnt2_X5 - Envelope point
0
CELSIUS
EnvPnt2_Y5 - Envelope point
0
CELSIUS
EnvPnt2_X6 - Envelope point
0
CELSIUS
EnvPnt2_Y6 - Envelope point
0
CELSIUS
EnvPnt2_X7 - Envelope point
0
CELSIUS
EnvPnt2_Y7 - Envelope point
0
CELSIUS
EnvPnt2_X8 - Envelope point
0
CELSIUS
EnvPnt2_Y8 - Envelope point
0
RPS
rps2 - Actual rotor speed coming from inverter
0
AMPERE
Mc2 - Current motor current [A]
0
kW
MP2 - Current motor consumption [kW]
0
CELSIUS
Drt2 - Current drive temperature [°C]
0
PSD circuit 2: the last alarm log
0
PSD circuit 2: the last-but-1st alarm log
0
PSD circuit 2: the last-but-2nd alarm log
0
PSD circuit 2: the last-but-3rd alarm log
0
MotTyp2 - BLDC circ.2 Carel Database ID
0
EEV_Protection_Circ1 - ExV protection status on circ.1
(1=NONE, 2=LOWSH, 3=LOP, 4=MOP, 5=HITCOND)
0
EEV_Protection_Circ2 - ExV protection status on circ.2
(1=NONE, 2=LOWSH, 3=LOP, 4=MOP, 5=HITCOND)
0
EEV_Reg_Circ1 - ExV control status on circ.1
0
EEV_Reg_Circ2 - ExV control status on circ.2
0
CELSIUS
AFE2 - Evap.2 frost temp.
0
CELSIUS
User delivery common water temperature
0
PERCENT
PwrRunCircs_Perc - Circuit capacity percentage by
compressors ON
0
CELSIUS
AFC2 - Cond.2 frost temp
0
CELSIUS
AFE1 - Evap.1 frost temp.
0
CELSIUS
AFC1 - Cond.1 frost temp
0
IOcfgPrbWrn - I/O probe confi guration warnings
0
CELSIUS
W_UsrTempRegPID - Water temperature value used
by control
Defrost status of circ 1
0
PERCENT
Capacity request using analogue input on circuit 1
0
Firmware B version on expansion board
0
Firmware B version on main board
-
-
Power+ circuit 1 error code
-
-
Power+ circuit 2 error code
-
-
Demande de puissance au compresseur AC – Circ 1
-
-
Demande de puissance au compresseur AC – Circ 2
FRE
Tab. 7.c
103