Index Size
Acronym
762
1
AI_CfgLim-
Max_Grp2_Slv
763
1
AI_CfgLim-
Max_Grp1_Slv
764
1
UnitTyp_Lim-
Max
765
2
U084
767
2
SEtU
769
1
U088
770
2
F026
772
2
U085
774
2
U086
776
2
U087
818
2
U090
820
2
U091
822
2
U092
817
1
U089
788
1
Hc90
789
1
Hc91
791
1
E073
815
1
E072
824
1
C081
825
1
C082
826
2
PwrReq_AC_Slv REAL
7.3
Input Register
Index Size Acronym
0
2
HuP1
2
2
HuP2
4
2
H1C1
6
2
H1C2
8
2
H2C1
10
2
H2C2
12
2
dSt1
14
2
Sct1
16
2
dSt2
18
2
Sct2
20
2
dSP1
22
2
ScP1
24
2
Cnd1
26
2
EuP1
28
2
dSP2
30
2
ScP2
32
2
Cnd2
34
2
EuP2
36
2
HSP1
38
1
C045
39
1
UnitCompTyp_Lim-
Max
40
2
HFn1
42
2
HFn2
46
2
SEtA
48
2
SSH1
50
1
Opn1
51
2
SSH2
53
1
Opn2
54
2
rUSr
56
2
dUSr
58
1
PwrReq_MC
59
1
PwrOut_MC
65
2
Fan1Req
67
2
Fan2Req
69
2
WoutMixVlv
71
1
UnitStatus
72
2
Comp1Circ1HrsR
74
2
Comp2Circ1HrsR
76
2
SrcFan1Circ1HrsR
78
1
FrcCompDesta-
bil_Circ1
102
Tableaux supervision
Min
Max
DataType
R/W
Value
Value
USINT
R/W 10
USINT
R/W 8
USINT
R/W 4
REAL
R/W 23
REAL
R/W 23
USINT(0..2)
R/W 0
REAL
R/W -40
REAL
R/W 2
REAL
R/W 5
REAL
R/W 20
REAL
R/W 0
REAL
R/W 0
REAL
R/W 100
USINT(0..2)
R/W 0
USINT
0
8
R/W 0
USINT
0
8
R/W 0
UINT
0
99
R/W 0
REAL
0
99,9
R/W 0
USINT
0
100
R/W 100
USINT
0
100
R/W 30
0
100
R/W --
Min
Max
DataType
Value
Value
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
UDINT
UINT
USINT
UDINT
UDINT
REAL
REAL
UINT
REAL
UINT
REAL
REAL
USINT
USINT
REAL
REAL
REAL
USINT
UDINT
UDINT
UDINT
UINT
Init
UoM
Description
Value
AI_CfgLimMax_Grp2 - Lim max probe group 2 secondary
AI_CfgLimMax_Grp1 - Lim max probe group 1 secondary
UnitTyp_LimMax - Lim max unit type
CELSIUS
U084 - Automatic changever threshold (type 1) (°C)
CELSIUS
SEtU - Automatic changeover set point (type 2,3) (°C)
U088 - Frost heater position
CELSIUS
F026 - Compressor cut-off by outside temperature
DELTAKELVIN U085 - Automatic changeover deadband (°C)
CELSIUS
U086 - Automatic changeover set point low limit (°C)
CELSIUS
U087 - Automatic changeover set point high limit (°C)
PERCENT
U090 - Analogue capacity request off set
PERCENT
U091 - Analogue capacity request min value
PERCENT
U092 - Analogue capacity request max value
U089 - Analogue capacity request input type (0=0-5V, 1=0-10V,
2=4-20mA)
HC90 - Display value selection - Large area
Hc91 - Display value selection - Small area
DELTA- KELVIN E072 - High superheat alarm activation threshold
MINUTE
E072 - High superheat alarm activation threshold
%
C081 – Limite maximale de la demande au compresseur AC
%
C082 – Limite minimale de la demande au compresseur AC
%
Demande envoyée au 2e circuit pour la sortie analogique
Init
R/W
UoM
Description
Value
R
0
HOUR
HuP1 - User pump 1 operating hours
R
0
HOUR
HuP2 - User pump 2 operating hours
R
0
HOUR
H1C1 - Comp.1 circ.1 operating hours
R
0
HOUR
H1C2 - Comp.2 circ.1 operating hours
R
0
HOUR
H2C1 - Comp.1 circ.2 operating hours
R
0
HOUR
H2C2 - Comp.2 circ.2 operating hours
R
0
CELSIUS
dSt1 - Discharge temp. probe on circ.1
R
0
CELSIUS
Sct1 - Suction temp. on circ.1
R
0
CELSIUS
dSt2- Discharge temp. probe on circ.2
R
0
CELSIUS
Sct2 - Suction temp. on circ.2
R
0
BAR
dSP1 - Discharge press. probe on circ.1
R
0
BAR
ScP1 - Suction press. on circ.1
R
0
CELSIUS
Cnd1 - Cond. temp. probe (or press. probe converted
value) on circ.1
R
0
CELSIUS
EuP1 - Evap. temp. probe (or press. probe converted
value) on circ.1
R
0
BAR
dSP2 - Discharge press. probe on circ.2
R
0
BAR
ScP2 - Suction press. on circ.2
R
0
CELSIUS
Cnd2 - Cond. temp. probe (or press. probe converted
value) on circ.2
R
0
CELSIUS
EuP2 - Evap. temp. probe (or press. probe converted
value) on circ.2
R
0
HOUR
HSP1 - Source pump 1 operating hours
R
0
C045 - Refrigerant type (3=R407C, 4=R410a, 6=R290,
10=R744, 22=R32)
R
0
UnitCompTyp_LimMax - Limit max of UnitCompTyp
variable
R
0
HOUR
HFn1 - Source fan 1 circ.1 operating hours
R
0
HOUR
HFn2 - Source fan 1 circ.2 operating hours
R
0
CELSIUS
SEtA - Actual set point used by temp. control
R
0
DELTAKELVIN SSH1 - Suction superheat on circ.1
R
0
PERCENT
Opn1 - EEV position on circ.1
R
0
DELTAKELVIN SSH2 - Suction superheat on circ.2
R
0
PERCENT
Opn2 - EEV position on circ.2
R
0
CELSIUS
rUSr - Return water temp. from user
R
0
CELSIUS
dUSr - Delivery water temperature to user
R
0
PERCENT
PwrReq_MC - MC capacity request
R
0
PERCENT
PwrOut_MC - MC output capacity
R
0
PERCENT
Fan1Req - Inverter request source fan circ.1
R
0
PERCENT
Fan2Req - Inverter request source fan circ.2
R
Water output mixing valve (from tank)
R
0
UnitStatus - Unit status (0=OFF from remote DI, 1=OFF
from keypad, 2=OFF from scheduler, 3=OFF from BMS,
4=OFF from CH/HP changeover mode, 5=OFF from
alarm, 6=Unit defrosting, 7=Unit ON, 8=Manual mode)
R
0
HOUR
Comp1Circ1HrsR - Comp.1 circ.1 operating hours (partial)
R
0
HOUR
Comp2Circ1HrsR - Comp.2 circ.1 operating hours (partial)
R
0
HOUR
SrcFan1Circ1HrsR - Source fan 1 circ.1 operating hours
(partial)
R
Destabilisation status for circ.1 (0=No comp. forcing
request , 1=Check if forcing is possible , 2=Enable to
force comp., 3=Wait status)
Tab. 7.b
μchiller +0300053FR rel. 2.4 - 09.10.2023