Index Size
Acronym
740
1
Hc51
741
1
Hc52
742
1
Hc53
743
1
Hc54
744
1
Hc55
745
1
Hc56
746
1
Hc61
747
1
Hc62
748
1
Hc63
749
1
Hc64
750
1
Hc65
751
1
Hc66
752
1
Hc31
753
1
Hc32
754
1
Hc34
755
1
Hc35
756
1
Hc41
757
1
Hc42
758
1
Hc43
759
1
Hc44
760
1
Hc45
761
1
Hc47
μchiller +0300053FR rel. 2.4 - 09.10.2023
Min
Max
DataType
R/W
Value
Value
USINT(0..11)
R/W 1
USINT(0..11)
R/W 1
USINT(0..11)
R/W 1
USINT(0..11)
R/W 1
USINT(0..11)
R/W 1
USINT(0..11)
R/W 1
USINT(0..8)
R/W 1
USINT(0..8)
R/W 1
USINT(0..8)
R/W 1
USINT(0..8)
R/W 1
USINT(0..8)
R/W 1
USINT(0..8)
R/W 1
USINT
R/W 0
USINT
R/W 0
USINT
R/W 0
USINT
R/W 0
USINT
R/W 0
USINT
R/W 0
USINT
R/W 0
USINT
R/W 0
USINT
R/W 0
USINT
R/W 0
Init
UoM
Description
Value
Hc51 - Digital output 1 confi g. (0= Not used, 1=Comp. 1 circ.
1, 2=Comp. 2 circ. 1, 3=User heater step 1, 4=User pump 1,
5=Source, 6=Frost heater, 7=4way valve, 8=Oil equal. valve,
9=Freecooling valve, 10=General alarm, 11=User pump 2
Hc52 - Digital output 2 confi g. (0= Not used, 1=Comp. 1 circ.
1, 2=Comp. 2 circ. 1, 3=User heater step 1, 4=User pump 1,
5=Source, 6=Frost heater, 7=4way valve, 8=Oil equal. valve,
9=Freecooling valve, 10=General alarm, 11=User pump 2
Hc53 - Digital output 3 confi g. (0= Not used, 1=Comp. 1 circ.
1, 2=Comp. 2 circ. 1, 3=User heater step 1, 4=User pump 1,
5=Source, 6=Frost heater, 7=4way valve, 8=Oil equal. valve,
9=Freecooling valve, 10=General alarm, 11=User pump 2
Hc54 - Digital output 4 confi g. (0= Not used, 1=Comp. 1 circ.
1, 2=Comp. 2 circ. 1, 3=User heater step 1, 4=User pump 1,
5=Source, 6=Frost heater, 7=4way valve, 8=Oil equal. valve,
9=Freecooling valve, 10=General alarm, 11=User pump 2
Hc55 - Digital output 5 confi g. (0= Not used, 1=Comp. 1 circ.
1, 2=Comp. 2 circ. 1, 3=User heater step 1, 4=User pump 1,
5=Source, 6=Frost heater, 7=4way valve, 8=Oil equal. valve,
9=Freecooling valve, 10=General alarm, 11=User pump 2
Hc56 - Digital output 6 confi g. (0= Not used, 1=Comp. 1 circ.
1, 2=Comp. 2 circ. 1, 3=User heater step 1, 4=User pump 1,
5=Source, 6=Frost heater, 7=4way valve, 8=Oil equal. valve,
9=Freecooling valve, 10=General alarm, 11=User pump 2
Hc61 - Digital output 1 secondary confi g. (0= Not used, 1=Comp.
1 circ. 2, 2=Comp. 2 circ. 2, 3=User heater step 2, 4=User pump 2,
5=Source, 6=Frost heater, 7=4way valve, 8=Oil equal. valve
Hc62 - Digital output 2 secondary confi g. (0= Not used, 1=Comp.
1 circ. 2, 2=Comp. 2 circ. 2, 3=User heater step 2, 4=User pump 2,
5=Source, 6=Frost heater, 7=4way valve, 8=Oil equal. valve
Hc63 - Digital output 3 secondary confi g. (0= Not used, 1=Comp.
1 circ. 2, 2=Comp. 2 circ. 2, 3=User heater step 2, 4=User pump 2,
5=Source, 6=Frost heater, 7=4way valve, 8=Oil equal. valve
Hc64 - Digital output 4 secondary confi g. (0= Not used, 1=Comp.
1 circ. 2, 2=Comp. 2 circ. 2, 3=User heater step 2, 4=User pump 2,
5=Source, 6=Frost heater, 7=4way valve, 8=Oil equal. valve
Hc65 - Digital output 5 secondary confi g. (0= Not used, 1=Comp.
1 circ. 2, 2=Comp. 2 circ. 2, 3=User heater step 2, 4=User pump 2,
5=Source, 6=Frost heater, 7=4way valve, 8=Oil equal. valve
Hc66 - Digital output 6 secondary confi g. (0= Not used, 1=Comp.
1 circ. 2, 2=Comp. 2 circ. 2, 3=User heater step 2, 4=User pump 2,
5=Source, 6=Frost heater, 7=4way valve, 8=Oil equal. valve
Hc31 - Analogue input 1 confi g. (0= Not used, 1= Source water
delivery temp., 2= Outside temp., 3= Discharge temp., 4=
Condensing temp., 5= Suction temp., 6= Evaporation temp., 7=
Return water temp. from user, 8= Delivery water temp. to user)
Hc32 - Analogue input 2 confi g. (0= Not used, 1= Source water
delivery temp., 2= Outside temp., 3= Discharge temp., 4=
Condensing temp., 5= Suction temp., 6= Evaporation temp., 7=
Return water temp. from user, 8= Delivery water temp. to user)
Hc34 - Analogue input 4 confi g. (0= Not used, 1= Source water
delivery temp., 2= Outside temp., 3= Discharge temp., 4=
Condensing. temp., 5= Suction temp., 6= Evaporation temp., 7=
Condensing press., 8= Evaporating press., 9= Return water temp.
from user, 10= Delivery water temp. to user)
Hc35 - Analogue input 5 confi g. (0= Not used, 1= Source water
delivery temp., 2= Outside temp., 3= Discharge temp., 4=
Condensing. temp., 5= Suction temp., 6= Evaporation temp., 7=
Condensing press., 8= Evaporating press., 9= Return water temp.
from user, 10= Delivery water temp. to user)
Hc41 - Analogue input 1 confi g. on Secondary board (0= Not used,
1= Source water delivery temp., 2= Outside temp., 3= Discharge
temp., 4= Condensing temp., 5= Suction temp., 6= Evaporation
temp., 7=Common delivery temp., 8= Delivery water evap.2 temp.)
Hc42 - Analogue input 2 confi g. on Secondary board (0= Not used,
1= Source water delivery temp., 2= Outside temp., 3= Discharge
temp., 4= Condensing temp., 5= Suction temp., 6= Evaporation
temp., 7=Common delivery temp., 8= Delivery water evap.2 temp.)
Hc43 - Analogue input 3 confi g. on Secondary board (0= Not used,
1= Source water delivery temp., 2= Outside temp., 3= Discharge
temp., 4= Condensing temp., 5= Suction temp., 6= Evaporation
temp., 7=Common delivery temp., 8= Delivery water evap.2 temp.)
Hc44 - Analogue input 4 confi g. on Secondary board (0= Not used,
1= Source water delivery temp., 2= Outside temp., 3= Discharge
temp., 4= Condensing. temp., 5= Suction temp., 6= Evaporation
temp., 7= Condensing press., 8= Evaporating press., 9= Common
delivery temp., 10= Delivery water evap.2 temp.)
Hc45 - Analogue input 5 confi g. on Secondary board (0= Not used,
1= Source water delivery temp., 2= Outside temp., 3= Discharge
temp., 4= Condensing. temp., 5= Suction temp., 6= Evaporation
temp., 7= Condensing press., 8= Evaporating press., 9= Common
delivery temp., 10= Delivery water evap.2 temp.)
Hc47 - Analogue input 7 confi g. on Secondary board (0= Not
used, 1= Source water delivery temp., 2= Outside temp., 3=
Discharge temp., 4= Condensing temp., 5= Suction temp., 6=
Evaporation temp., 7=Common delivery temp., 8= Delivery water
evap.2 temp.)
FRE
101
Tableaux supervision