2 Sensor with Teach function (factory setting)
Factory default values
1 Teach input
1 switching output
Switching function
Switch point (SP)
Hysteresis
Delay time
Damping
Installation
Before mounting and removing the sensor, make sure that no
pressure is applied to the system .
Screw the sensor into a G¼ process connection. Tightening torque
recommended 25 Nm (max. 50 Nm).
Electrical connection
The unit must only be connected by an electrician.
The national and international regulations for the installation of
electrical equipment must be observed.
Voltage supply to EN50178, SELV, PELV.
Disconnect power before connecting the unit.
Wiring:
BN
1
WH
2
4
BK
BU
3
for setting to the desired pressure value (pin 2)
semiconductor output, p-switching (pin 4)
normally open (normally closed selectable)
25% of value of measuring range;
(is set to new value by Teach function)
2% of value of measuring range
0 s
0.06 s
Core colours of ifm sockets:
1 = BN (brown),
L +
2 = WH (white),
3 = BU (blue),
IN (Teach)
4 = BK (black).
OUT