NGC-30-CRM/-CRMS installation instructions
NGC-30-CRM/CRMS
MSB
TB 12
TB 7
1
2
1
Alarm output
2
Relay outputs (5x)
3
LEDs (9x)
4
Fuse
5
12 Vdc Inputs (2x)
6
End of Line (EOL) jumper
7
RS-485 Communications
8
Line & ground-fault sensor
inputs (5x)
9
RTD Inputs
bk
Address Switches
Power Supply
The power supply connector (TB19) is a
dual two pin connector. Either connector
allows for power in (pin #1 (+), pin #2 (–)
and bussing of power to other NGC-30-CRM
modules).
Note: Power supply must be sized correctly
based on the number of NGC-30-CRM/-CRMS
modules.
RS-485 Communications
The RS-485 connector (TB6) is a dual three
pin connector. Either connector allows for
RS-485 input signals (pin #1 (shield), pin #2
(+), pin #3 (–)) and bussing of RS485 signal
to other NGC-30-CRM modules.
End of Line (EOL) Jumper
If this device (NGC-30-CRM/-CRMS) is the last
device in the RS-485 network, the J1 jumper
needs to be moved from terminals 2 & 3 to
terminals 1 & 2.
bk
LSB
TB 1
1 2 3
TB 19
TB 6
TB 13
TB 14
3
4 5 6
7
LED functions
1
2 1
2
1 2 3
1 2 3
Normal
End of Line
position
position
1
2
3
1
2
3
TB 2
TB 3
TB 4
TB 5
TB 15
TB 16
TB 17
8
178 mm
(7.00")
9
273 mm
(10.75")
nVent.com/RAYCHEM
EN
DE
FR
RU
|