3-Wire Connection: Direct Wire
Use this method only if local codes permit connecting ground
conductor to neutral supply wire.
1. Pull the wires through the conduit on cord/conduit plate on
bottom of range. Allow enough slack to easily attach the wiring
to the terminal block.
A
D
A.
Terminal block
B.
Ground-link
screw
C.
Cord/conduit
plate
2. Attach terminal lugs to line 2 (red), bare (green) ground, and
line 1 (black) wires. Loosen (do not remove) the setscrew on
the front of the terminal lug and insert exposed wire end
through bottom of terminal lugs. Securely tighten setscrew to
torque as shown in the following Bare Wire Torque
Specifications chart.
C
A.
Terminal lug
B.
Setscrew
C.
Line 2 (red) wire
Bare Wire Torque Specifications
Wire Awg
8 gauge copper
6 gauge aluminum
B
F
E
D. Line 2 (red) wire
E. Bare (green) ground wire
F. Line 1 (black) wire
A
B
D
E
D. Bare (green) ground wire
E. Line 1 (black) wire
Torque
25 lbs-in (2.8 N-m)
35 lbs-in (4.0 N-m)
3. Use 3/8" (9.5 mm) nut driver to connect the bare (green)
ground wire to the center terminal block post with one of the
10-32 hex nuts.
A
B
C
4. Connect line 2 (red) and line 1 (black) wires to the outer
terminal block posts with 10-32 hex nuts.
5. Using a torque wrench, tighten the hex nuts to a
recommended torque of 20 in-lbs (2.3 N-m).
6. Securely tighten hex nuts.
IMPORTANT: Verify the tightness of the hex nuts.
7. Replace terminal block access cover.
8. Reconnect power.
C
A.
D. Bare (green) ground wire
10-32 hex nut
E. Line 1 (black)
B.
Line 2 (red)
F. Terminal lug
C.
Ground-link
screw
F
E
D
17