■ 15 TECHNICAL DATA
OUTPUTS, SIGNALS, ALARMS
Visual:
•
Various LEDs for displaying the operational and alarm status
USB:
•
Memory read-out
Wired network:
•
CXI: read-out via the Internet by means of a suitable cloud
application. Go to www.resus.eu for technical network
requirements.
Volt-free contact for:
•
Building management system, remote surveillance, other signal
transmitter (SMS module, audible alarm, flashing light ...), shutting
down of the boiler, ...
The alarm conditions are:
•
Corrosion rate too high (adjustable)
•
Fault in the corrosion monitor
•
End of the service life of the metal coupon on the probe
CHARACTERISTICS
Physical:
•
Pressure range: 0 to 6 bar
•
Temperature range: 5 to 95 °C, integrated temperature
compensation
•
Environment: 0 to 45 °C, no condensation
•
Storage: -20 to 60 °C
•
Probe: PPS
•
Logger: PC
•
Coupon: Fe
•
Threaded connector: brass CW614N
•
See also dimensions