If the connection is correct, the green LED at the Ethernet port is lit
and the orange LED blinks.
3. Enter the date of the installation on page 90 .
4. Using the green terminal connector, the integrated, volt-free
contact can be connected to an external safety circuit (e.g. building
management, external signalling device or the safety circuit of the
heat source). The circuit is closed in case of normal operation of
the corrosion monitor, and is interrupted in case of an alarm, as well
as when there is no power supply.
CAUTION! The volt-free contact with a normally open contact is
closed during the operation of the corrosion monitor. In the case
of an alarm, the volt-free contact interrupts the external safety
circuit of max. 48 VDC/VAC, 2 A, 60 W.
NOTE: If the safety circuit of the heat generator is connected,
and the mains supply to the corrosion monitor fails (e.g. faulty
cables, power supply, fuse, etc.), the heating system can no
longer work. In this case, the 'ALARM IGNORE' function may
also not work. This can be rectified by a bridge in the terminal
connector. The volt-free contact will thereby be closed, so that
the heat generator can function again. The corrosion monitor will
still not function, however.