5.3 Technical data table
Model
Number of elements
Max. heating capacity
Min. heating capacity
Max. heat output
Min. heat output
Efficiency Pmax (80-60°C)
Efficiency 30%
Max. working pressure in heating
Min. working pressure in heating
Max. heating temperature
Heating water content
Heating expansion vessel capacity
Heating expansion vessel prefilling pressure
Max. working pressure in DHW
Min. working pressure in DHW
DHW flow rate Dt 25°C
DHW flow rate Dt 30°C
Protection rating
Power supply voltage
Electrical power input
Electrical power input in DHW
Empty weight
Combustion chamber length
Combustion chamber diameter
Pressure loss on fume side
46
EN
ATLAS D ECO 30 SI UNIT
no.
3
kW
26.6
kW
21.0
kW
25.0
kW
20.0
%
93.9
%
98.2
bar
3
bar
0.8
°C
100
liters
20
liters
10
bar
1
bar
9
bar
0.3
l/min
14.3
l/min
11.9
IP
X0D
V/Hz
230/50
W
200
W
200
kg
160
mm
350
mm
300
mbar
0.11
cod. 3541Q544 - Rev. 02 - 05/2024
ATLAS D ECO SI UNIT
ATLAS D ECO 42 SI UNIT
4
39.4
21.0
37.0
20.0
94.0
97.4
3
0.8
100
25
10
1
9
0.3
21.2
17.7
X0D
230/50
200
200
200
450
300
0.35
(Q)
(Q)
(P)
(P)
(PMS)
(tmax)
(PMW)