GB
2.4
Functional description
Pos
Designation
1
Air/ water heat exchanger
3
Solenoid valve
5
Water outlet
Cooling function process
•
The warm interior air of the switch cabinet is blown by the fan (2) over the air/ water heat exchanger (1) and
cools off.
•
In correspondence with the selected setpoint temperature, a solenoid valve (3) regulates the cooling water flow
(4)/(5), and thus the cooling capacity. The cooled air is then diverted back into the ambient air.
•
Condensing water must be diverted through the condensate drain (6) and is collected in a
bottle. This condensate collecting bottle is available as an accessory from Pfannenberg.
For Pfannenberg part numbers for accessory orders, see Ordering of
Operating manual PWS and PWI 6502 T 785408480 © Pfannenberg GmbH
Figure 3 - Refrigerant circuit
Pos
Designation
2
Fan
4
Water inlet
6
Condensation drain
condensate collecting
accessory
parts.
Page 6 / 31