VAS 6380B / VAS 6381B
If the tank pressure deviates by more than 1 bar from the normal
pressure, the non-condensing gases must be discharged manually, as
otherwise proper operation of the device is no longer guaranteed.
!
CAUTION! Risk of injury
Wear protective gloves and goggles.
Wear hearing protection at pressures above 10 bar.
Ensure adequate ventilation.
Do not inhale escaping gases.
Keep the device away from ignition sources.
1. Take off the front panel:
Undo the screws (D) on the control panel and lift it up. Then undo the
screws (E) on the bottom of the front panel and take it off.
2. Locate the NCG valve on top of the large refrigerant tank.
3. Pull the ring for approximately 10 s.
4. Mount the front cover again.
EN
D
E
Service tasks
D
E
125