Steps for connecting the AC connector.
1.
Remove the AC connector from the accessory bag.
a.
The fully disassembled AC connector is shown below:
b.
AC terminal head
Fig. 33. AC connector.
According to the above table, select a suitable cable,
c.
remove the insulation sleeve from the AC cable about
50 mm, and remove the insulation from the end of the
L/PE/N cables about 8 mm, as shown in Fig. 34:
Cable diameter: 10-14 mm.
Fig. 34. Cable stripping.
Insert the stripped end of the three cables into the
d.
corresponding hole of the terminal head (yellow-green
cable into the PE port, phase into the L port and neutral
into the N port). Pull from the cable to check that it is
properly connected, as shown in Fig. 35:
Fig. 35. Inserting the bare wire into the terminal.
According to the direction of the arrow, push the threaded
e.
sleeve until it connects to the AC terminal head, and then
turn the cable gland clockwise to lock it, as shown in Fig. 36:
Fig. 36. Connecting and fastening the sleeve on the
AC terminal.
USER MANUAL
Threaded sleeve
Cable gland
Str i p p ed l e n g th : 8 mm.
50 mm.
Connect the AC connector to the inverter's AC terminal;
f.
a click indicates that the connection is in place, as shown
in Fig. 37:
Fig. 37. Connecting the AC connector to the inverter's AC terminal.
Intersperse the relevant AC protections according to
g.
current regulations. The differentials must be type B.
Connect the other end of the hose to the AC circuit breaker
h.
in the junction box, downstream of the connection's IGA.
ICP
IGA
Fig. 38. Electrical wiring diagram.
ID
PIAs
EQX2 SOLAR INVERTERS CONNECTED TO THE GRID