Ditemp Dt3 With Alarm Outputs (Optional) - SIKA DiTemp DT3 Série Notice D'utilisation

Masquer les pouces Voir aussi pour DiTemp DT3 Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

DiTemp DT3 with alarm outputs (optional)

6
DiTemp DT3 with alarm outputs (optional)
WARNING! Risk of injury or material damage!
Due to the battery supply of the devices, this measuring system must not be used for the
active control of a process, as the operating time of the battery is limited if frequent
switching operations are carried out.
The DiTemp DT3 can optionally be equipped with programmable switching contacts. This
additional function enables simple switching point programming "on site".
Programming is carried out with the enclosed magnetic pen. The magnetic pen ensures that
no arbitrary or unauthorized changes can be made.
Enter password
 Touch the °C symbol with the magnetic pen for approx. 5 s.
PAS appears briefly and the 1st digit of the password flashes. The default password is
"000".
SIKA logo
°C symbol (short)
°C symbol (long)
Con appears for confirmation. Err appears if the entry is incorrect.
Menu overview
Main menu
AL1 (alarm 1)
AL2 (alarm 2)
Parameters
PC
A1t / A2t
A1L / A2L
A1h / A2h
- 24 -
PAN
Description
Password code
Alarm contact
Alarm value
Digit is increased by 1
Switch to the next position
Password is confirmed
Hysteresis
© SIKA • Ba_DiTemp-DT3 • 03/2020
DiTemp DT3
Parameters
PC
A1t
A1L
A1h
A2t
A2L
A2h
Adjustment range
000...999
off
LoA (normally closed)
hiA (normally open)
See measuring range
∆T = 0...50 K

Publicité

Table des Matières
loading

Table des Matières