WATER CONNECTION
Water connection is performed with hose threaded G1/2. The water supply must be equipped with a separate
valve which is freely available and within range of the device. The equipment includes a check valve.
• Water hardness must be in range 0,5 - 5 ° French degree.
IF HIGHER, IT IS NECESSARY USE WATER SOFTENING SYSTEM.
• Water pressure must be within range 50 - 250kPa.
• Volume of chlorine in the water shall not be higher than 10ppm, or you risk bath surface damage
• Acidity of water must be higher than 7 pH.
• Electrical conductivity: 50 - 2000uS/cm (20°C)
• The connection must be made according to directive EN 1717 and with valid to national directives for aqua-
culture.
PIPE FOR GAS CONNECTION
It must fi rst determine if the appliance is made for the same type of gas that will be used and thus conforms
to the indications on the label the type of gas to be used.
The conversion of gas pan to another type of gas you need to check if it corresponds to the type of gas
bearing, which is recommended in this guide.
Connecting the appliance to the gas distribution must be towable to a steel or copper tube complying with
applicable national requirements. This must be controlled on regular basis and changed if needed. Every
appliance must be equipped with shut-off valve and quick shut-off valve. Quick shut-off valve must be freely
accessible and within reach of the device. After installation, is necessary to check whether there is a gas leak.
To fi nd a gas leak you can use soapy water or spray for gas leak detection.
Do not use corrosive substances!! All our appliances are carefully controlled. Gas type, pressure and of the
categories listed named on the technical information plate.
Liquid gas connection:
Pressure for liquid gas connection must be 28 or 30 mbar for propane/butane and 37 mbar for propane. It
is necessary to check the technical label ,gauge the pressure and check the parameters of the nozzle is
installed with the required parameters of the nozzle according to the manufacturer's. If the pressure is lower
than 25mbar or higher than 37 mbar, THE APPLIANCE SHALL NOT TO BE CONNECTED.
Gas Connection:
Pressure for methane connection must be 18 or 20 mbar. It is necessary to check the technical label ,gauge
the pressure and check the parameters of the nozzle is installed with the required parameters of the nozzle
according to the manufacturer's. If the gas pressure is lower than 15mbar or higher than 22,5 mbar, THE
APPLIANCE SHALL NOT TO BE CONNECTED.
7