1
AUTO
POWER
MANUAL
MANUAL
> 3 s
2
2
LED OFF
EN
DIP Switch
1. Network
A
Three phase network with neutral (3P+N)
B
Single phase network (1P+N)
2. Prio Set
A
Priority source 1
B
No priority
3. Order Mod
A
Control mode impulse logic
B
Control mode contactor logic
4. Δ U/ Δ F
A
Threshold setting at ±10% of nominal voltage / ±5% of
nominal frequency (hysteresis value is 20% of ΔU/ΔF)
B
Threshold setting at ±20% of nominal voltage / ±10% of
nominal frequency (hysteresis value is 20% of ΔU/ΔF)
5. ODT
A
Delay time in position 0: 2 second (0DT = 2 s)
B
Delay time in position 0: 0 second (0DT = 0 s)
6. FT
A
Transfer delay time in case of source failure: 0 s
B
Transfer delay time in case of source failure: 5 s
7/8. RT
AA
Return delay time for restoring the prioritized source: 0 s
AB
Return delay time for restoring the prioritized source: 5 s
BA
Return delay time for restoring the prioritized source: 15 s
BB
Return delay time for restoring the prioritized source: 30 s
Settings / Parametrieren / Paramétrage / Parametrizar / 确定参数
LED OFF
10%
0s
A A
3P+N
S2
PULSE
5%
2s
0s
A
A
A
A
A
A
5s
A B
20%
NO
15s
1P+N
MAINT.
10%
0s
5s
B A
PRIO
B
B
B
B
B
B
30s
B B
1
ORDER
3
WORK
3P+N
A
1P+N
B
中文
DIP 开关
A
三相电网 3P+N
B
单相电网 1P+N
A
电源 1 优先
B
无优先级
A
控制模式脉冲逻辑
B
控制模式开关逻辑
A
电压阀值设置为额定电压的±10% /
频率阀值设置为额定频率的±5% (滞后值为 ΔU/ΔF 的 20%)
B
电压阀值设置为额定电压的± 20% /
频率阀值设置为额定频率的±10% (滞后值为 ΔU/ΔF 的 20%)
A
0 位置停留 2 秒 (0DT = 2 秒)
B
0 位置停留 0 秒 (0DT = 0 秒)
A
电源故障转换延时 0 秒
B
电源故障转换延时 5 秒
AA
优先电源恢复返回延时 0 秒
AB
优先电源恢复返回延时 5 秒
BA
优先电源恢复返回延时 15 秒
BB
优先电源恢复返回延时 30 秒
SET DIP
4
1 2 3 4 5 6 7 8
OK
A
B
PROG
2
3
4
5
6
7 8
PRIO
ORDER
U
ODT
FT
RT
SET
MOD
F
10%
0s
A A
S1
PULSE
5%
2s
0s
A
A
A
A
A
5s
A B
20%
NO
15s
B A
MAINT.
10%
0s
5s
PRIO
B
B
B
B
B
30s
B B
L1V30800010-02 / 552047B
13