FUNCTIONS FOR SWINGING GATE OPENERS - Dip Switch B n°1=OFF
Description
AUTOMATIC / SEMI-AUTOMATIC
Automatic Cycle: with one impulse from the open command the gate opens and stops in
Pause mode for the time set on the Dwell Trimmer. When this time expires the gate automatically
closes
Semi-automatic Cycle: with one impulse from the open command the gate opens and is
stopped open. To close the gate you must give a close pulse.
INVERSION OF DIRECTION DURING OPENING:
IMPORTANT: (*) if limit switches are connected to terminals 9
and 10, this function cannot be used (see page 16)
Gate travel is reversed only in the opening cycle. The function is
aimed at protecting those areas of moviment between the opening
gates and possible fixed obstacles ( perimeter walls or gate posts)
to prevent crashing.
On expiring of the Dwell time, the gate closes (if automatic mode
is pre-selected: Dip-A No. 3=ON)
PEDESTRIAN OPENING FOR MOTOR M1 ONLY
With the gates in closed position: a first opening command opens the M1 gate for pedestrians
A second opening pulse will operate the gate fully open, along with the other gate, M2 motor.
The function "Pedestrian Opening " is not in service during the first operation cycle, after a
power failure.
RE-CLOSING AFTER PASSAGE BETWEEN THE PAIR OF PHOTOCELLS: during the opening cycle
and in Dwell time (DIP-A No.3 = ON)
This function allows automatic re-closing of the gates 3 seconds after passage between
the pair of photocells. If a 2nd pair of photocells is also installed, they must be enabled
by setting Dip-A No. 9=ON.
DSA: PHOTOCELL AUTOMATIC CONTROL:
For the DSA control (Device for Safety Auto-test) it is necessary to
connect only the photocell transmitters to this output and to select
Dip-B No.4=ON: if this function is enabled, Elpro X and Elpro XE will
check that all the connected photocell devices are cleared from
obstacles, and properly working, before starting any gate movements,
otherwise the gates are not started.
DEADMAN mode:
The open/close operations are achieved "by holding on a command switched" (the relay is
not self-retaining) and consequently the user must be actively present during all automation
movements until the push-button or the key-switch is released.
STROKE REVERSING PULSE ON OPENING:
This function facilitates disengagement of the Electrical lock when the gate is fully closed,
even in Pedestrian Open mode: the wings of the closed gate are pushed to close for 2
seconds before opening.
Installation in Blocks of Flats:
This is a function for intense use with frequent inversions of direction: when this function is
enabled it takes into account the remaining motor run time when there is an inversion of
direction or passage between the photocells.
OPENING THROUGH EXTERNAL CLOCK:
Connection: connect the Clock NO contact in parallel
with OPEN terminal No. 4 and COMMON No. 3, activating
automatic re-closure with Dip-Switch No. 3=ON.
Operation: program the opening time on the clock.
When this present time comes up the gate will open and
remain open (the flashing light turns off) and will not
accept any other command (not even radio
commands) until the time set on the clock expires. When
this time expires the gate automatically closes after the
pause time.
page 18
XE
X
UNIVERSAL ELECTRONIC CONTROL BOXES
230V 50/60Hz SINGLE-PHASE
3 4
8 9 10
NC
contact
during
opening
15
16
24V ac output for photocell TX
assigned to the DSA control
External clock
NO
Dip-Switches and LED signals of the various functions
DIP-SWITCH-A N°3:
ON: Closes automatically
OFF: Semi-automatic
3
Dwell Trimmer: adjusts pause time for
Automatic mode from 1s up to 220 s
DIP-SWITCH-B N°3:
ON: Gate travel reversing in opening activated
by the NC safety devices connected to terminals
9 and 10
3
OFF:Normal operation with limit switches
DIP-SWITCH-A N°6:
ON: M1 Pedestrian gate opening
OFF: Pedestrian opening excluded
6
DIP-SWITCH-A N°9 and N°11:
ON: Enables the 2nd pair of photocells
OFF: 2nd pair of photocells not used
9
ON: Automatic re-closure after passage
between the pair of photocell after 3 seconds
11
OFF: No automatic re-closure
DIP-SWITCH-B N°4:
ON: Activates the DSA safety control
OFF: Deactivates DSA safety control
4
DIP-SWITCH-B N°2:
ON: Activates the deadman function
OFF: Deactivates the deadman function
2
DIP-SWITCH-A N°7:
ON: Stroke reversing pulse enabled for 2 s
OFF: Stroke reversing pulse disabled
7
DIP-SWITCH-A N°12:
ON: Motor run time memory enabled
OFF: Motor run time memory disabled
12
DIP-SWITCH-A N°3:
ON: Closes automatically
3
Important: use only and always
with Dip-switch No.3 = ON