DANGER
Disconnect power before servicing the product.
Failure to do so could result in death or
electrical shock.
General information
x The models may be powered at 240V or 208V.
This cooktop does not require a neutral connection. If
the cooktop is to be completely enclosed in a cabinet,
feed the cooktop cable through the opening in the
cabinet. Make the electrical connection following the
appropriate steps for your installation.
Your cooktop must be connected to the proper
electrical voltage and frequency as specified in the
table on the right.
Figure 12. Location of serial tag
Connect with copper wire only
If the house has aluminum wiring, follow the
procedure below:
1. Connect the aluminum wiring to the copper wire
by using special connectors designed and
Underwriters Laboratories-listed for joining copper
to aluminum. Follow the electrical connector
manufacturer's recommended procedure.
2. Aluminum/copper connection must conform with
local codes and industry- accepted wiring
practices.
Electrical Connections
WARNING
The flexible conduit (supplied) 3 feet long (100 cm)
located at the right rear of the cooktop bottom box
should be connected directly to junction box. Do not
cut the conduit. A U.L - or CSA - listed conduit
connector must be provided at each end of the power
supply cable (at the cooktop and at the junction box.)
A time delay fuse or circuit breaker is recommended.
Do not ground to a gas pipe. Do not have a fuse in the
grounding or neutral circuit.
Fuse both supply (phase) lines.
WARNING
Improper connection of aluminum house wiring to
the copper leads can result in a serious problem.
Model
Model
240 V 60 Hz
240 V 60 Hz
F3RK24B1
6,0kW
24"
ECCB330H1ASS
F3RK24S1
6,1kW
30"
6,7kW
ECCB330H1ABL
F3RK30B1
30"
6,7kW
ECCB336H1ASS
36"
9,4kW
36"
F3RK36B1
9,4kW
ECCB336H1ABL
National Fire Protection Association
Batter/march Park Quincy, Massachusetts 02269
A three-wire, single phase, 240 Volt 60 cycle electrical
system (properly circuit protected to meet Local
Codes of NFPA No.70) must be provided. Unit must
be properly grounded in accordance with local wiring
code. The chart below recommends the minimum
circuit protector and wire size if the appliance is the
only unit on the circuit. If smaller sizes of wire are
used, the unit efficiency will be reduced and a fire
hazard may be created. It is advisable that the
electrical wiring and hookup be accomplished by a
competent electrician.
Installation Manual
ENGLISH
Power Supply
Power Supply
Approval
208 V 60 Hz
Approval
208 V 60 Hz
code
code
25A
4,5Kw
21,5A
514Y40NN
514T40IA
25,5A
4,6Kw
22A
514Y40IL
28A
5,03kW
24A
514T40NA
514T40IA
28A
5,03kW
24A
514T40NA
514V50IC
39A
7,06kW
34A
514V50IC
39A
7,06kW
34A
514V50NC
514V50NC
9