Maintenance, Repair, Disposal - Rechner Sensors TRUE Level KFS-1 Série Manuel D'utilisation

Masquer les pouces Voir aussi pour TRUE Level KFS-1 Série:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

FAQ
Situation
U
-LED does not light
B
The yellow LED above the jumper does not
switch off during the adjustment
The yellow LED above the jumper does not
switch on during the adjustment
output-signal is inverted
Unusual measurement values during the
change of products or the refilling
Unusual measurement values in general
Probe can not recognize the medium

Maintenance, repair, disposal

• Maintenance for this device is not necessary. Take care, that the active area and the "free zone" are clear
of deposits
• It is not possible to repair the device. If you have got problems, please contact directly your customer
service.
• Please dispose of the device in a way that is environmentally friendly according to the national regulations
Cause and remedy
Supply voltage is missing
BE-Cable is not connected (correctly)
Please check the connection to the container and
the amplifier
- The probe is mounted too close to the container wall
Please make sure, that the min. distance and the
inactive zones are observed
- The assignment of the colour markings (white /
black) are interchanged
Please make sure, that the assignment is
according to the labeling on the board
Change-over switch „output" is in the wrong position
Different types / states of the product (different DC)
at the reference and the measuring range (e.g.
liquid / solid)
The holder is mounted within the reference or
measuring range
The holder can only be mounted in the provided
range (IBH)
Adjustment failed. Please adjust the probe again.
It is necessary to do this in the order. previously
described
19