Instruction CF-MC Master Controller
6.2 Relays for Pump & Boiler Control
Activate Relay mode on Master Controller ( g. 23)
• Use the menu selection button
ashes
• Activate Relay mode by pressing OK . Relay LED
Select the Relay con guration
• Press the output selection button
Relay con gurations
• NO LEDs: The relays are not used
• 1 LED: Pump control
• 2 LEDs: Boiler control
• 3 LEDs: Pump and boiler control
• 4 LEDs: Pump control with 2min. start/stop delay
• 5 LEDs: Pump and boiler control, with 2min. start/stop delay on pump
(default)
• Activate selected relay con guration by pressing OK
Note: If the pump relay is active, the Master Controller will run a pump motion
program every 3rd day and it will last for one minute.
6.3 Input for Global Standby and Heating & Cooling
Activate Input mode on Master Controller ( g. 23)
• Use the menu selection button
ashes
• Activate Input mode by pressing OK . Input LED
Select the Input con guration
• Press the output selection button
Input con gurations
• 1 LED: The input ports are not used
• 2 LEDs: The Master Controller will switch to cooling mode when the input
for heating/cooling is activated ( g. 2 - )
• 3 LEDs: The Master Controller will switch to a xed set room temperature
at 8 °C for all Room Thermostats when the input for global standby is
activated ( g. 2 - )
• 4 LEDs: The Master Controller will switch to cooling mode when the input
for heating/cooling is activated ( g. 2 - ). In heating mode the Master
Controller will switch to a xed set room temperature at 8 °C for all Room
Thermostats when the input for global standby is activated ( g. 2 - )
(default)
• Activate selected input con guration by pressing OK