G
AERASGARD
®
RFTM - LQ - PS - CO2 - Modbus | Telegrams
Function 08 Diagnostics
The following sub function codes are supporte
Sub Function
Parameter
Code
00
Echo of transmission data
(Loopback)
01
Restart Modbus
(Reset listen-only mode)
04
Activation listen-only mode
10
Delete counter
11
Counter bus telegrams
12
Counter communication errors
(Parity, CRC, frame errors, etc.)
13
Counter exception telegrams
14
Counter slave telegrams
15
Counter telegrams without answer
Function 17 Report Slave ID
Composition of answer telegram
Byte Nr.
Parameter
00
Number of bytes
Slave ID (device type)
01
02
Slave ID (device class)
Status
03
04
Version number (release)
Version number (version)
05
06
Version number (index)
Data Type
Answer
Echo data
Echo telegram
No answer
Echo telegram
Unsigned 16 Bit
All valid bus telegrams
Faulty bus telegrams
Unsigned 16 Bit
Error counter
Unsigned 16 Bit
Unsigned 16 Bit
Slave telegrams
Broadcast messages (address 0)
Unsigned 16 Bit
Data Type
Answer
Unsigned 8 Bit
6
Unsigned 8 Bit
14 = AERASGARD
Unsigned 8 Bit
60 = AERASGARD
Unsigned 8 Bit
255 = RUN, 0 = STOP
Unsigned 8 Bit
1...9
Unsigned 8 Bit
1...99
Unsigned 8 Bit
1
26
®
MODBUS
®
/ AERASREG
®