RFTM - LQ - PS - CO2 - Modbus | Telegrams
TELEGRAMS
Function 04 Read Input Register
Register
Parameter
3x0001
CO2
3x0002
CO2
3x0003
VOC [%]
3x0004
VOC [%]
3x0005
Temperature
3x0006
Temperature
3x0007
relative humidity
3x0008
relative humidity
3x0009 * not assigned
3x0010 *
not assigned
3x0011 *
Potentiometer position
3x0012
VOC [ppb]
3x0013
VOC [ppb]
3x0014
Particulate Matter (PM)
3x0015
Particulate Matter (PM)
* only for device version with setpoint potentiometer
Function 05 Write Single Coil
Register
Parameter
0x0001
Reset (Auto zero) CO2
0x0002
Reset (Auto zero) VOC
0x0003
Automatic calibration (Automatic) CO2
0x0004
not assigned
0x0005
VOC sensibility "low"
0x0006
VOC sensibility "medium"
0x0007
VOC sensibility "high"
0x0008
LCD-backlighting
System of units
0x0009
Temperature
0x0010
Particulate Matter (PM) particle size
Sampling 4 s
Signed 16 Bit
Filtering 32 s
Signed 16 Bit
Sampling 4 s
Signed 16 Bit
Filtering 32 s
Signed 16 Bit
Sampling 4 s
Signed 16 Bit
Filtering 32 s
Signed 16 Bit
Sampling 4 s
Signed 16 Bit
Filtering 32 s
Signed 16 Bit
no filtering
Signed 16 Bit
Sampling 4 s
Unsigned 16 Bit
Filtering 32 s
Unsigned 16 Bit
Sampling 4 s
Signed 16 Bit
Filtering 32 s
Signed 16 Bit
SI
→ Imperial
[°C]
→ [°F]
24
Data Type
Value
350...5000
350...5000
0...1000
0...1000
0...500
320...1220
0...500
320...1220
0...1000
0...1000
0...1000
0...60 000
0...60 000
0...1000
0...1000
Data Type
Value
Bit 0
0 / 1
Bit 1
0 / 1
Bit 2
0 / 1
Bit 4
0 / 1
Bit 5
0 / 1
Bit 6
0 / 1
Bit 7
0 / 1
Bit 8
0 / 1
Bit 9
0 / 1
Range
350...5000 ppm
350...5000 ppm
0.0...100.0 % VOC
0.0...100.0 % VOC
0.0... +50.0 °C
+32.0...+122.0 °F
0.0... +50.0 °C
+32.0...+122.0 °F
0.0...100.0 % RH
0.0...100.0 % RH
0.0...100.0 %
0...60 000 ppb
0...60 000 ppb
0...1000 µg/m
3
0...1000 µg/m
3
Range
OFF - ON
OFF - ON
OFF - ON
OFF - ON
OFF - ON
OFF - ON
OFF - ON
SI (Default) -
Imperial
PM 2,5 / PM 10