Installation; Sauna Heater Installation - Tylo Air Notice D'installation

Masquer les pouces Voir aussi pour Air:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 21
Positioning the air intake vent
Position the air intake vent straight through the wall behind the
center line of the heater (see Figure 6).
Vent size for a family sauna approx. 125 cm².
The air circulation from the door must work together with the hot
air circulation from the heater.
1
3
Figure 6: Positioning the air intake and exhaust vents
1.
Air intake vent positioning.
2.
Air exhaust vent positioning through the sauna wall.
3.
Air exhaust vent positioning through the cavity.
4.
Air exhaust vent positioning via duct.
Air exhaust vent positioning.
DANGER! The air exhaust vent must not lead
outdoors. This could cause the ventilation
direction to be reversed, which may negatively
affect the heater temperature cut-out.
DANGER! Any gap above the sauna ceiling
should not be sealed without leaving at least one
vent hole on the same wall as the sauna door!
Position the air exhaust vent:
at the maximum possible distance from the air intake vent,
e.g. diagonally (see Figure 6).
high on the wall or in the ceiling (see Figure 6).
so that it vents into the space that the door and air intake
vent open into.
The air exhaust vent must have the same area as the air intake vent.
Make sure that the air exhaust vent is open.
Mechanical ventilation is not recommended due to the risk of poor
air exchange, which may negatively affect the heater temperature
cut-out.

INSTALLATION

Sauna heater installation

It is easiest to prepare for installation with the heater lying down.
To install the heater:
1.
Lay the heater down with the front facing upwards.
2.
Undo the screws and open the cover (see Figure 7).
2
Figure 7: Opening/closing the cover
4
Connect the heater using standard wiring (Fk or EKK) approved
for fi xed installation.
Any single wires (Fk) must be protected in electrical conduits (VP)
up to the heater.
3.
Connect the electrical cable (1) to the terminal (2) (see Figure 8)
according to the wiring diagram (see the Connection/wiring
diagram section, page 11).
Figure 8: Circuit board
4.
Run the cables for the control panel and the temperature
sensor through the cable grommets (3). Connect the control
panel cable (4) to one of the four RS485 contacts (positions
5-8) (see Figure 8) according to the wiring diagram (see the
Connection/wiring diagram section).
WARNING! Always check that the heater is
connected to the correct main/phase voltage!
6
4
5
7
2
1.
Electrical cable
2.
Terminal for connection of electrical cable
3.
Cable grommet (x6)
4.
Control panel cable
5.
Modular contacts for connection of control panel,
sensor, etc.
6.
Sensor cable
7.
Light cable (if relevant)
8.
Terminal for connection of lighting (if relevant)
9.
Strain relief connector for cables to modular contacts (x2)
10. Strain relief connector for electrical cable
9
9
3
1
10
8

Publicité

Table des Matières
loading

Table des Matières