Configuring the Heat Pump Heating System

6 Configuring the Heat Pump Heating System
The menus for "Outputs", "Inputs" and "Special functions" as well
as the extended setting menu can be set at the configuration
level. The extended menu level for technicians is called by

6.1 Settings

Depending on the system configuration, the full "Settings" menu
contains the following inquiries:
simultaneously pressing the button combination (MENUE) and
(ENTER ↵) (for approx. 5 seconds)
Select the desired menu item with the arrow buttons and confirm
with the ENTER button (↵).
System-specific parameters
Menu for setting the time.
Level for setting operating modes
Selects the operating mode
It is also possible to make changes directly
using the modus button.
Duration of party mode in hours
After the set period has elapsed, the system
returns automatically back to automatic
operation again.
Duration of vacation mode in days
After the set period has elapsed, the system
returns automatically to automatic operation
again.
Settings for heating circuit 1
The following heating regulation options are
available for heating circuit 1:
* Return temperature regulation based on the
external temperature and the set heating curve
* Return temperature regulation via a fixed-
setpoint (horizontal heating characteristic
curve)
* Return temperature regulation based on the
room temperature in a reference room
The heating curve end point should be set
according to the design of the heating system.
This should be done by entering the maximum
return temperature, which is the product of the
maximum calculated flow temperature minus
the temperature difference in the heating
system (spread).
Sets the desired return set temperature when
fixed-setpoint regulation is selected
Sets the desired room set temperature when
room temperature regulation is selected
Sets the minimum return temperature when
room temperature regulation is selected
Setting range
Display
International 24 h
Always
display
Always
Cooling
Always
Summer
Auto
Party
Vacation
HG 2
0
Always
... 4 ...
72
0
Always
... 15 ...
150
Always
External
Always
temperature
Fixed-setpoint
Room temperature
20 °C
External temperature
... 30 °C ...
70 °C
15 °C
Fixed-setpoint
... 40 °C ...
60 °C
15 °C
Room regulation
... 20 °C ...
30 °C
15 °C
Always
... 20 °C ...
30 °C
6.1