WPM Econ5
1 Important Information
During commissioning, observe the respective national
safety
regulations
and
regulations, particularly VDE 0100, as well as the technical
connection requirements of the utility companies (EVU) and
network operators!
The heat pump manager should only be operated in dry
rooms with temperatures ranging between 0 °C and 35 °C.
Ensure that no condensation forms on the device.
All sensor connection leads can be extended in accordance
with the electrical documentation to up to 50 m with
0.75 mm² Cu cables with routing type B2 and an ambient
temperature of 35 °C. Sensor leads should not be installed
next to power cables.
2 Heat Pump Manager: Scope of Supply
The heat pump manager is available in three versions.
Integrated in the heat pump casing
Heat pump manager for wall mounting
for a heat pump heating system
Heat pump manager for wall mounting
for a heat pump system for heating.
The scope of supply of the wall-mounted heat pump manager
includes:
3 Assembly
3.1 Attaching the wall-mounted heat pump manager (heating)
The controller is attached to the wall with the 3 screws and
dowels (6 mm) included in the scope of supply. The following
installation procedure must be followed to avoid soiling or
damaging the controller:
Mount the dowels for the upper fastening eyelet at operator
level.
Screw the screw into the dowel so that the controller can be
mounted.
Mount the controller by the upper fastening eyelet.
Mark the position of the side drill-holes.
Unhook the controller.
Mount the dowels for the side drill-holes.
Remount the controller at the top and tighten the screws.
EN-2
the
applicable
VDE
safety
452115.66.26 FD 9404
To ensure that the frost protection function of the heat pump
works properly, the heat pump controller must remain
connected to the power supply and the flow must be
maintained through the heat pump at all times.
The switching contacts of the output relay are interference-
suppressed.
Therefore,
resistance of the measuring instrument, a voltage can also
be measured when the contacts are open. However, this will
be much lower than the line voltage.
Terminals J1 to J11, J24 - J26 and the terminal strip X3 of
the heating controller N1 are connected to a low voltage
supply. If, due to a wiring error, the line voltage is mistakenly
connected to these terminals, the heat pump manager will
be destroyed.
Heat pump manager with casing
3 dowels (6 mm) with screws for wall mounting
Sensor for the outside temperature, demand sensor R2.2
and with domestic hot water cylinder R3
Operator's manual and operating instructions for users
Installation and commissioning instructions for technicians
Electrical documentation
Fig. 3.1:
Dimensions of the wall-mounted heat pump manager (heating)
depending
on
the
internal